2004-11-12 00:00:00******** UNSAT **************
  
 1)NOTE: PLEASE SEE PLANS CONTAINING
 TITLE BLOCKS, ARE REQUIRED TO BE SIGNED,
 DATED AND SEALED BY PERSON RESPONSIBLE
 FOR PLANS.
 FS 481.221, 471.025
 PLEASE ALSO SEE FAC 61G15-23.002,
 61G1-16.004 FOR MISSING LICENSE #'S AS
 REQUIRED UNDER FS 481.219 AND 471.023
 FOR FIRMS ETC.
 THIS IS REQUIRED ON ALL SHEETS WHEATHER
 OR NOT COMMENT IS MADE BY OTHER
 REVIEWERS.
 FBC 104.2.1
  
  
 2) NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
  
 3)NOTE: PLEASE SHOW ALL RECEPTS
 SERVING KITCHEN COUNTERSPACE AS GFI/GFI
 PROTECTED PER 210.8A-6
  
  
 4) NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 5)NOTE: PLEASE SEE NFPA -72 8-1.4.2 FOR
 LOCATIONS OF SD'S. A MIN OF 3' FROM BATH
 DRS.
  
 6)NOTE: PLEASE CORRELATE LOADS/OCP AND
 AWG ON PANEL SCHEDULE.
 PLEASE SEE INSTA-HOTS UNITS, SHOWS
 2P30A
 WITH 11.8KW LOAD?
 PLEASE ALSO SEE LOADS SHOWN FOR COND
 UNIST AS 10KW, THIS SHOULD BE FOR AHU'S
 HOWEVER THESE ARE NOT LISTED.
 PLEASE ALSO SEE 424.3B FOR OCP ETC.
 310.16, 240.4
  
 7)NOTE: PLEASE SEE 210.52E FOR MISSING
 FRONT AND REAR RECEPTS.
  
 8)NOTE: PLEASE SEE 210.8 FOR ALL RECEPTS
 TO BE GFI/ GFI PROTECTED.
  
 9)NOTE: PLEASE SEE 250.6,250.24, AN
 EQUIPMENT GRND IS NOT INSTALLEDFROM
 METER TO FIRST MEANS OF DISC.
  
 10)NOTE: PLEASE SEE 2002 NEC 210.12,
 PLEASE LIST ARC FAULT PROETCTION ON
 PANEL SCHEDULE.
 NOTES MENTIONS SD' TO BE WIRED INTO
 KITCHEN/BATH LTS? THIS WOULD REQUIRED
 THESE TO ALSO BE ARC FAULT PROTECTED.
  
 11)NOTE: PLEASE SHOW DISCONNECTING MEANS
 FOR INSTA-HOT UNITS. IF OCP, THEN THESE
 MUST MEET 110.26.
 PLEASE ALSO SEE MANUFACTS SPECS FOR
 CLEARENCE REQ',MENTS FOR UNITS.
  
 PLEASE SEE ONE SET OF ELECTRICAL PLANS
 HAVE BEEN REDLINED FOR MOST OF THE ABOVE
 ITEMS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD MAY BE SUBMITTED FOR
 REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]