Date |
Text |
2004-11-12 00:00:00 | ******** UNSAT ************** |
| |
| 1)NOTE: PLEASE SEE PLANS CONTAINING |
| TITLE BLOCKS, ARE REQUIRED TO BE SIGNED, |
| DATED AND SEALED BY PERSON RESPONSIBLE |
| FOR PLANS. |
| FS 481.221, 471.025 |
| PLEASE ALSO SEE FAC 61G15-23.002, |
| 61G1-16.004 FOR MISSING LICENSE #'S AS |
| REQUIRED UNDER FS 481.219 AND 471.023 |
| FOR FIRMS ETC. |
| THIS IS REQUIRED ON ALL SHEETS WHEATHER |
| OR NOT COMMENT IS MADE BY OTHER |
| REVIEWERS. |
| FBC 104.2.1 |
| |
| |
| 2) NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| RATED FOR THE AVAILABLE FAULT CURRENT. |
| PER 110.9/215.5 |
| |
| |
| 3)NOTE: PLEASE SHOW ALL RECEPTS |
| SERVING KITCHEN COUNTERSPACE AS GFI/GFI |
| PROTECTED PER 210.8A-6 |
| |
| |
| 4) NOTE: PLEASE LIST ALL THE REQ'D |
| DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| SCHEDULE. PER 210.52D, 210.11C3 |
| |
| 5)NOTE: PLEASE SEE NFPA -72 8-1.4.2 FOR |
| LOCATIONS OF SD'S. A MIN OF 3' FROM BATH |
| DRS. |
| |
| 6)NOTE: PLEASE CORRELATE LOADS/OCP AND |
| AWG ON PANEL SCHEDULE. |
| PLEASE SEE INSTA-HOTS UNITS, SHOWS |
| 2P30A |
| WITH 11.8KW LOAD? |
| PLEASE ALSO SEE LOADS SHOWN FOR COND |
| UNIST AS 10KW, THIS SHOULD BE FOR AHU'S |
| HOWEVER THESE ARE NOT LISTED. |
| PLEASE ALSO SEE 424.3B FOR OCP ETC. |
| 310.16, 240.4 |
| |
| 7)NOTE: PLEASE SEE 210.52E FOR MISSING |
| FRONT AND REAR RECEPTS. |
| |
| 8)NOTE: PLEASE SEE 210.8 FOR ALL RECEPTS |
| TO BE GFI/ GFI PROTECTED. |
| |
| 9)NOTE: PLEASE SEE 250.6,250.24, AN |
| EQUIPMENT GRND IS NOT INSTALLEDFROM |
| METER TO FIRST MEANS OF DISC. |
| |
| 10)NOTE: PLEASE SEE 2002 NEC 210.12, |
| PLEASE LIST ARC FAULT PROETCTION ON |
| PANEL SCHEDULE. |
| NOTES MENTIONS SD' TO BE WIRED INTO |
| KITCHEN/BATH LTS? THIS WOULD REQUIRED |
| THESE TO ALSO BE ARC FAULT PROTECTED. |
| |
| 11)NOTE: PLEASE SHOW DISCONNECTING MEANS |
| FOR INSTA-HOT UNITS. IF OCP, THEN THESE |
| MUST MEET 110.26. |
| PLEASE ALSO SEE MANUFACTS SPECS FOR |
| CLEARENCE REQ',MENTS FOR UNITS. |
| |
| PLEASE SEE ONE SET OF ELECTRICAL PLANS |
| HAVE BEEN REDLINED FOR MOST OF THE ABOVE |
| ITEMS. |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW SHEETS INTO COMPLETE |
| SETS FOR REVIEW AND STAMPING. |
| ONE SET OF OLD MAY BE SUBMITTED FOR |
| REFERENCE. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |
| NOTES MENTIONS SD'S TO BE WIRED TO |
| |
| 7 |