2004-11-29 00:00:00 | CHECKLIST: |
| 1-PAY IMPACT FEES TO PALM BEACH COUNTY. |
| BRING BACKSTAMPED DRAWINGS AND PAID |
| RECEIPT. |
| |
| 2-NEED RECORDED NOTICE OF COMMENCEMENT. |
| |
| 3-RIGHT ELEVATION DON'T MATCH PLANS. |
| THERE IS AN ADDITIONAL WINDOW SHOWN ON |
| THE ELEVATION. REVISE AS REQUIRED. |
| |
| 4-SPECIFY CONCRETE SLAB JOINTS OR |
| SPECIFY WWM SUPPORTS & SPACING AS REQ'D |
| BY SEC. 1909.3 FBC 2001. |
| |
| 5-LINTEL SHEDULE DON'T MATCH SIZES. SEE |
| FOUNDATION PLANS AND LINTEL SCHEDULE |
| AND |
| REVISE AS REQUIRED. |
| |
| 6-SPECIFY BEAM AT NOOK AREA. SECTION |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| |
| 7-TYPICAL WALL SECTION: A) SPECIFY |
| FIREBLOCKING AS REQUIRED BY SECTION |
| 705.3.1.1 FBC 2001. |
| B) INDICATE MIN. FOOTING EMBEDMENT AS |
| REQUIRED BY SEC. 1804.1.3 FBC 2001. |
| |
| 8-REVISE PORCH DETAIL TO MATCH PORCH |
| CONSTRUCTION SHOWN ON PLANS. PORCH |
| SHOWN |
| IS FOR WOOD FRAMED STRUCTURE. |
| |
| 9-SOIL TEST REPORT. REVISE SQUARE FOOT |
| OF PROPOSED STRUCTURE. SEE PLANS. |
| |
| 10-PROVIDE 2X STRUCTURAL BUCK DETAIL |
| FOR |
| SWING DOORS AS REQUIRED ON THE PRODUCT |
| APPROVAL. |
| |
| 11-PROVIDE FLORIDA/LOCAL PRODUCT |
| APPROVAL FOR: |
| A) ENTRY DOORS WITH DRAWINGS THAT MATCH |
| THOSE SUBMITTED FOR FLORIDA BUILDING |
| COMMISION REVIEW AND APPROVAL. |
| B) DOOR W/ SIDELITES AS SHOWN ON PLANS. |
| C) 45 DEGREES FIXED WINDOW SYSTEM. |
| D) GARAGE SIDE DOOR. |
| |
| 12-PROVIDE COMPLETE INFORMATION FOR |
| STORM SHUTTERS INCLUDING:A) KEY PLAN |
| AND |
| COMPLETE INSTALLATION SCHEDULE (SEE |
| ATTACHED SAMPLE) |
| B)INDICATE ON DWGS SPECIFIC MOUNTING |
| CONDITIONS AND ANCHOR TYPE AND SPACING |
| TO BE USED ACCORDING TO THE DESIGN |
| PRESSURES, EDGE DISTANCE, CONNECTION |
| TYPE, PANEL SPAN AND STRUCTURE TO BE |
| ATTACHED TO (MASONRY OR CONCRETE). |
| |
| 13-SHEET 1/10: UPDATE INFORMATION. SEE |
| COMMENTS ON PLANS. |
| |
| 14-SPECIFY SIZE OF WINDOW TO BE |
| INSTALLED AT NOOK AREA. SECTION |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| |
| 15-UPDATE TRUSS ANCHOR SCHEDULE. SEE |
| LATEST CATALOGUE. OR, PROVIDE COMPLETE |
| ENGINEERING FOR TYPE AND NUMBER OF |
| FASTENERS THAT DIFFER FROM APPROVED AND |
| PUBLISHED ON MANUFATURER'S CATALOGUE. |
| SEE COMMENTS ON PLANS. |
| **CLARIFY WHY ARE THERE ADDITIONAL |
| FASTENERS SHOWN ON RIGHT HAND SIDE |
| COLUMN? |
| |
| 16-WHICH ARE THE CONNECTORS A3 AND A4. |
| THEY ARE NOT SHOWN ON TRUSS ANCHOR |
| SCHEDULE. |
| |
| 17-ROOF FRAMING PLAN AND PORCH DETAIL |
| TO |
| MATCH. THEY SPECIFY DIFFERENT NUMBER OF |
| 2X12'S. REVISE AS REQUIRED. SEE |
| COMMENTS |
| ON PLAN. |
| |
| 18-OWES $203.82 FOR UPDATED VALUATION |
| AND RADON FEES. |
| |
| 19-OWNER/AGENT TO SIGN AND DATE ENERGY |
| CALCULATIONS AS REQUIRED BY SEC. 103.1.2 |
| CHAPTER 13 FBC 2001. |
| |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| JULIO GOMEZ AT 805-6712. |