2004-11-29 00:00:00CHECKLIST:
 1-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING BACKSTAMPED DRAWINGS AND PAID
 RECEIPT.
  
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
  
 3-RIGHT ELEVATION DON'T MATCH PLANS.
 THERE IS AN ADDITIONAL WINDOW SHOWN ON
 THE ELEVATION. REVISE AS REQUIRED.
  
 4-SPECIFY CONCRETE SLAB JOINTS OR
 SPECIFY WWM SUPPORTS & SPACING AS REQ'D
 BY SEC. 1909.3 FBC 2001.
  
 5-LINTEL SHEDULE DON'T MATCH SIZES. SEE
 FOUNDATION PLANS AND LINTEL SCHEDULE
 AND
 REVISE AS REQUIRED.
  
 6-SPECIFY BEAM AT NOOK AREA. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 7-TYPICAL WALL SECTION: A) SPECIFY
 FIREBLOCKING AS REQUIRED BY SECTION
 705.3.1.1 FBC 2001.
 B) INDICATE MIN. FOOTING EMBEDMENT AS
 REQUIRED BY SEC. 1804.1.3 FBC 2001.
  
 8-REVISE PORCH DETAIL TO MATCH PORCH
 CONSTRUCTION SHOWN ON PLANS. PORCH
 SHOWN
 IS FOR WOOD FRAMED STRUCTURE.
  
 9-SOIL TEST REPORT. REVISE SQUARE FOOT
 OF PROPOSED STRUCTURE. SEE PLANS.
  
 10-PROVIDE 2X STRUCTURAL BUCK DETAIL
 FOR
 SWING DOORS AS REQUIRED ON THE PRODUCT
 APPROVAL.
  
 11-PROVIDE FLORIDA/LOCAL PRODUCT
 APPROVAL FOR:
 A) ENTRY DOORS WITH DRAWINGS THAT MATCH
 THOSE SUBMITTED FOR FLORIDA BUILDING
 COMMISION REVIEW AND APPROVAL.
 B) DOOR W/ SIDELITES AS SHOWN ON PLANS.
 C) 45 DEGREES FIXED WINDOW SYSTEM.
 D) GARAGE SIDE DOOR.
  
 12-PROVIDE COMPLETE INFORMATION FOR
 STORM SHUTTERS INCLUDING:A) KEY PLAN
 AND
 COMPLETE INSTALLATION SCHEDULE (SEE
 ATTACHED SAMPLE)
 B)INDICATE ON DWGS SPECIFIC MOUNTING
 CONDITIONS AND ANCHOR TYPE AND SPACING
 TO BE USED ACCORDING TO THE DESIGN
 PRESSURES, EDGE DISTANCE, CONNECTION
 TYPE, PANEL SPAN AND STRUCTURE TO BE
 ATTACHED TO (MASONRY OR CONCRETE).
  
 13-SHEET 1/10: UPDATE INFORMATION. SEE
 COMMENTS ON PLANS.
  
 14-SPECIFY SIZE OF WINDOW TO BE
 INSTALLED AT NOOK AREA. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 15-UPDATE TRUSS ANCHOR SCHEDULE. SEE
 LATEST CATALOGUE. OR, PROVIDE COMPLETE
 ENGINEERING FOR TYPE AND NUMBER OF
 FASTENERS THAT DIFFER FROM APPROVED AND
 PUBLISHED ON MANUFATURER'S CATALOGUE.
 SEE COMMENTS ON PLANS.
 **CLARIFY WHY ARE THERE ADDITIONAL
 FASTENERS SHOWN ON RIGHT HAND SIDE
 COLUMN?
  
 16-WHICH ARE THE CONNECTORS A3 AND A4.
 THEY ARE NOT SHOWN ON TRUSS ANCHOR
 SCHEDULE.
  
 17-ROOF FRAMING PLAN AND PORCH DETAIL
 TO
 MATCH. THEY SPECIFY DIFFERENT NUMBER OF
 2X12'S. REVISE AS REQUIRED. SEE
 COMMENTS
 ON PLAN.
  
 18-OWES $203.82 FOR UPDATED VALUATION
 AND RADON FEES.
  
 19-OWNER/AGENT TO SIGN AND DATE ENERGY
 CALCULATIONS AS REQUIRED BY SEC. 103.1.2
 CHAPTER 13 FBC 2001.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.