Date |
Text |
2004-11-16 00:00:00 | DENIED |
| |
| |
| 1)IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| PLANS MUST BE STAMPED BY COUNNTY EVEN IF |
| NO FEES ARE DUE. |
| |
| 2) SUBMIT A SIGNED AND SEALED SURVEY |
| SHOWING THE LOCATION OF THE STRUCTURE ON |
| THE LOT. |
| |
| 3) IF PLANS ARE DRAWN BY AN ARCHITECT, |
| THEY MUST BE SIGNED AND SEALED BY HIM |
| AND HAVE A TITLE BLOCK WITH ALL |
| INFORMATION REQUIRED BY FAC 61G-16.004. |
| |
| 4) FIRE BLOCKING IS REQUIRED AT THE |
| CONCEALED SPACES BETWEEN STRINGERS PER |
| FBC 2305.1.4. SPECIFY THIS ON PLAN. |
| |
| 5) THE NOTE ON A4 REQUIRES ARCHITECTS |
| APPROVAL FOR STUCCO FINISH. REVISE NOTE |
| IF THEIR IS NO ARCHITECT ON THIS JOB. |
| |
| 6) FBC 11-4.23.2 REQUIRES THE DOOR TO |
| THE HALF BATH ON THE FIRST FLOOR TO HAVE |
| A 29" CLEAR OPENING. |
| |
| 7) SPECIFY THE DIMENSIONS TO THE WALL |
| WITH THE ENTRY DOOR ON SHEET A1. |
| |
| 8) PLEASE CLARIFY ON THE ROOF NOTE ON |
| SHEETS A3,A4,A5 AND A6 WHAT THE @ |
| 24"O.C.IS REFERING TO. |
| |
| 9) SPECIFY THE MEAN ROOF HEIGHT ON THE |
| PLANS. |
| |
| 10) SPECIFY THE DIMENSIONS ON THE |
| FOUNDATION PLAN ON S1. |
| |
| 11) THE DETAIL FOR THE STEEL COLUMN SC2 |
| THAT IS SPECIFIED IN THE COLUMN SCHEDULE |
| AS BEING ON SHEET S1 IS NOT GIVEN. |
| |
| 12) ON SHEETS S1 AND S2 THE C1 8X16 |
| CONCRETE COLUMN IS SHOWN AS A DOUBLE |
| FILLED CELL MASONRY COLUMN. PLEASE |
| CORRECT. |
| |
| 13) THE COMPONENT AND CLADDING PRESSURES |
| GIVEN ON S2 CONFLICT WITH THOSE LISTED |
| ON S6. |
| |
| 14) TB-1 IS SPECIFIED ON THE SECOND |
| FLOOR FRAMING PLAN ON S2 BUT IS NOT |
| LISTED IN THE CONCRETE BEAM SCHEDULE. |
| |
| 15) ON S2 THE STEEL COLUMN CAP 'A' |
| REFERS TO DETAIL 3 ON S2, WHICH IS NOT |
| GIVEN. |
| |
| 16) PLEASE CLARIFY THE NOTE IN THE WOOD |
| BEAM SCHEDULE ON S2 THAT REFERS TO A 2X |
| 6 SECOND FLOOR WALL. |
| |
| 17) CORRECT THE TYPOS IN THE JAMB |
| DETAILS ON S2. SEE NOTATIONS ON THE |
| PLAN. |
| |
| 18) THE LATERAL (F2) VALUE FOR THE USP |
| HTA16-18 IS INCORRECT. IT IS 325. |
| |
| 19) THE MAXIMUM NEGATIVE PRESSURE FOR |
| ZONE 4 ON S2 IS SPECIFIED WITH A |
| POSITIVE SIGN. PLEASE CORRECT. |
| |
| 20) THE TRUSS ANCHOR ID MARKS ON THE |
| LOWER ROOF DO NOT INDICATE WHICH TRUSSES |
| THEY ARE TO BE USED ON. |
| |
| 21) CITY OF WPB AMENDMENTS TO FBC TABLE |
| 2306.1 REQUIRES 8D RING SHANK NAILS IN |
| ZONE 3 FOR A MEAN ROOF HEIGHT OF 25'. |
| |
| 22) THE OVERHEAD GARAGE DOOR FL PRODUCT |
| APPROVAL HAS THE WRONG INSTALLATION |
| DRAWING ATTACHED. SEE DRAWING #S LISTED |
| ON THE FL COVER SHEET AND THE WEBSITE |
| FOR THE CORRECT INFO. |
| |
| 23) THE FRENCH DOOR PRODUCT APPROVAL HAS |
| A JELD-WEN FL 498 COVER SHEET ON A PGT |
| NOA. PLEASE CORRECT. |
| |
| 24) THE INSTALLATION DRAWINGS FOR THE |
| OXO AND XO CONFIGURATIONS OF THE PGT |
| SGD-70 (SLIDING GLASS DOOR)ARE REQUIRED |
| IN ADDITION TO THE OXXO THAT WAS |
| SUBMITTED. |
| |
| IF YOU HAVE ANY QUESTIONS PLEASE CALL : |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |