2004-11-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT A-1 WATER RISER DIAGRAM SHOW TWO
 1/2 INCH LINES TO A FIXTURE NOT SHOWN ON
 THE FLOOR PLAN, AND HAS "WATER HAMPERS"
 INDICATED ON THEM. PLEASE CLARIFY.
 SECTION 104.2.1
 2) SHT A-1 WATER HEATER SHALL BE
 ACCESSIBLE. PLEASE SUMBIT A DETAIL
 SHOWING HOW THE HEATER WILL BE SERVICED
 AND REMOVED IF NEEDED. SECTION 501.4
 3) KITCHEN SINK SHALL BE ACCESSIBLE.
 SUBMIT A DETAIL SHOWING HEIGHT
 11-4.24.2
 KNEE CLEARANCE 11-4.24.3, SINK DEPTH
 11-4.24.4, CLEAR FLOOR SPACE (SHALL BE
 PROVIDED IN FRONT OF A SINK TO ALLOW
 FORWARD APPROACH. - SHALL EXTEND MAXIMUM
 OF 19 IN. UNDER THE SINK - FIG 32)
 SECTION 11-4.24.5, AND EXPOSED PIPES AND
 SURFACES 11-4.24.6
 4) ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS, AND LICENSE NUMBER
 ON EACH SHEET. FAC 61G15-23.002(2) AND
 FS 471.025
  
  