Plan Review Notes
Plan Review Notes For Permit 04100617
Permit Number 04100617
Review Stop E
Sequence Number 1
Notes
Date Text
2004-10-23 00:00:00****** UNSAT *******
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS. THERE ARE A COUPLE OF ITEMS NOT
 IDENTIFIED.
 PLEASE ALSO SEE 700.12E FOR CIRCUITING
 OF EM/EXT LTS. SOME SHOWN ON WITH
 GARAGE OUTLETS?
 PLEASE SEE POSSIBLE FIRE REVIEW COMMENTS
 FOR PLACEMENT OF EXIT SIGNS.NOTE ONLY:
  
 2)NOTE: PLEASE SEE CIRCUITING FOR RECEPT
 'S. PLEASE SEE 220.13 FOR 180VA PER
 DEVICE. PLEASE SEE # OF RECEPTS ON
 CIRCUITS WHICH SEEM TO OVERLOAD CIRCUIT-
 -S.MAX 1920 FOR A 20A CIR.
  
 3)NOTE: PLEASE SEE BBC DESIGNS IN TITLE
 BLOCK. PLEASE INCLUDE REQUIRED LICENSE
 #'S ? PER FS 481. ARCH/INT DESIGN.
 PLEASE ALSO SEE FAC 61G1-16.004,
 61G15-23.002 FOR ENGINEER.
 PLEASE SEE MISSING PRINTED NAME AND #.
 FBC 104.2.1
  
 PLEASE SEE POSSIBLE NOTES FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]