Plan Review Notes
Plan Review Notes For Permit 04100592
Permit Number 04100592
Review Stop P
Sequence Number 1
Notes
Date Text
2004-11-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT 1 CLEAR FLOOR SPACE FOR BREAK
 ROOM SINK SHALL BE FORWARD APPROACH NOT
 PARALLEL AS SHOWN. SECTION 11-4.24.5.
 2) SHT 2 SHOW CLEAR FLOOR SPACE FOR
 SINK. SECTION 11-4.24.5.
 3) SHT 7 IN THE INSTALLATION OR REMOVAL
 OF ANY PART OF A DRAINAGE SYSTEM, DEAD
 ENDS SHALL BE PROHIBITED.
 4) SHT 8 (SEE COMMENT #3).
 5) SUBMIT A DETAIL FOR THE SINKS SHOWING
 COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS. SHOW:
 A) HEIGHT 11-4.24.2
 B) KNEE CLEARANCE 11-4.24.3
 C) DEPTH OF SINK 11-4.24.4
 D) CLEAR FLOOR SPACE - WHICH SHALL BE
 PROVIDED IN FRONT OF A SINK TO ALLOW
 FORWARD APPROACH AND SHALL EXTEND A
 MAXIMUM OF 19" UNDERNEATH THE SINK.
 E) EXPOSED PIPES AND SURFACES
 11-4.24.6
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]