Plan Review Notes
Plan Review Notes For Permit 04100572
Permit Number 04100572
Review Stop E
Sequence Number 1
Notes
Date Text
2004-10-22 00:00:00***** UNSAT *****
  
 1)NOTE: PLEASE SEE ELECTRICAL CONTRACTOR
 SIGNED ON PERMIT APPLICATION.
 THIS REQUIRES AN ELECTRICAL REVIEW TO
 ISSUE ELECTRICAL PERMIT.
  
 2)NOTE: PLEASE SUBMIT LAYOUT SHOWING
 ALL MIN ELECTRICAL REQUIRED BY 2002 NEC.
 PLEASE INCLUDE ALL EXITS/EM LLTS AS
 MENTIONED IN LTRS. PLEASE CIRCUIT PER
 700.12E.
 SIGN CIRCUITS? 600.5
 SHOW WINDOW RECEPTS? 210.62, 220.12
  
 3)NOTE: PLEASE SEE FS 481.229, PLANS
 REQUIRED TO SIGNED, SEALED BY ARCH.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]