2004-10-28 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 04100572 |
| ADD: 603 VILLAGE BLVD |
| CONT: SOUTHAMPTON RESTORATION |
| TEL: (561)687-0505 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1STREVIEW |
| ACTION: DENIED |
| |
| 1) PROVIDE NOC RECORDED WITH THE CLERK |
| OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| |
| 2) PLANS, SPECIFICATIONS,REPORTS OR |
| OTHER DOCUMENTS PREPARED BY THE DESIGN |
| PROFESSIONAL AND BEING FILED FOR PUBLIC |
| RECORD SHALL HAVE THE SIGNATURE AND |
| SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| TO THE DOCUMENT. |
| FL STATE STAT: 61G15-23.002 ENGINEERS |
| FL STATE STAT: 61G16.003 ARCHITECTS |
| FL STATE STAT# 481.229 PLANS THAT INDI- |
| CATE OVER $25,000.00 OF WORK WILL ON |
| COMMERCIAL WORK WILL REQUIRE PLANS TO BE |
| SIGNED & SEALED BY A DESIGN PROFESSIONAL |
| |
| 3) 104.2.1.3* QUALITY OF BUILDING PLANS |
| PLANS SHALL BE DRAWN TO A MINIMUM 1/8" |
| SCALE. |
| |
| 4) 11-4.1.6(1)(B) |
| IF EXISTING ELEMENTS, SPACES, OR COMMON |
| AREAS ARE ALTERED, THEN EACH SUCH ALTER- |
| ED ELEMENT, SPACE, FEATURE OR AREA SHALL |
| COMPLY WITH THE APPLICABLE PROVISIONS OF |
| 11-4.1.1 TO 11-4.1.3 MINIMUM REQUIRE- |
| MENTS FOR NEW CONSTRUCTION. |
| DEFITION OF ALTERED- ANY CHANGE OR |
| MODIFICATION IN CONSTRUCTION OR OCCUPAN- |
| CY.THERE MAY BE DOORWAYS THAT MAY NOT |
| MEET THE REQUIREMENTS OF 11-4.13.6. |
| 11-4.13.6 MANEUVERING CLEARENCES |
| AT DOORS. MINIMUM MANEUVERING CLEARENCES |
| AT DOORS THAT ARE NOT AUTOMATIC OR |
| POWER-ASSISTED SHALL BE AS SHOWN IN |
| FIG. 25. THE FLOOR OR GROUND AREA WITH |
| IN THE REQUIRED CLEARENCES SHALL BE |
| CLEAR & LEVEL. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |