2004-10-28 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 1. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304. - SEE DRYER ROOM,
 WATER HEATER ROOM, AND FIREPLACE.
 2) SHUTOFF VALVES ARE REQUIRED UPSTREAM
 OF THE GAS REGULATORS. SECTION 409.7
 SHOW ON GAS RISER DIAGRAM.
 3) ALL DRAWINGS SHALL BEAR THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DESIGN. SECTION 104.2.1
  