Date Text
2004-10-21 00:00:00PROVISO:
 1.PLAN SHEET M-1 INDICATES CU-2
 LOCATED 5TH FLOOR PARKING LEVEL.PER
 2001 FBC(M) 303.4, EQUIPMENT LOCATED IN
 AREAS WHERE DAMAGE COULD OCCUR, SHALL BE
 PROTECTED BY APPROVED BARRIERS.
  
 2.NO COMBUSTIBLES ALLOWED ABOVE THE
 CEILING IN THE RETURN AIR PLENUM PER
 2001 FBC(M) 602.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.