Plan Review Notes
Plan Review Notes For Permit 04100422
Permit Number 04100422
Review Stop P
Sequence Number 1
Notes
Date Text
2004-11-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT P-1 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS, NOR DOES IT
 REFLECT THE FLOOR PLAN.
 A) BAR SINK IN FAMILY ROOM NOT SHOWN ON
 THE RISER DIAGRAM. SECTION 104.2.1
 B) VENT REQUIRED FOR EACH WASH MACHINE.
 SECTION 901.2.1, AND THE WASH MACHINE
 SHALL HAVE A CLEANOUT 4 FT. ABOVE THE
 FLOOR FOR ACCESS. SECTION 708.10
 C) WASH MACHINE AND LAUNDRY SINK DO NOT
 REFLECT THE FLOOR PLAN. THE W/M SHALL BE
 ON THE RIGHT SIDE AND THE LAUNDRY SINK
 SHALL BE ON THE LEFT SIDE. SECTION
 104.2.1
 D) KITCHEN PREP SINK IS MISLABLED AS A
 BAR SINK. SECTION 104.2.1
 E) LAVS IN THE MASTER BATH TO BOTH FACE
 INTO THE BATHROOM. SECTION 104.2.1
 F) BATHROOM #2 ALL FIXTURES SHALL LOOK
 INTO THE SAME ROOM AS SHOWN ON THE FLOOR
 PLAN. SECTION 104.2.1
 2) INDICATE WHERE THE SHOWER ON THE
 FLOOR PLAN OUTSIDE THE CABANA BATH
 DRAINS TO. SECTION 104.2.1
 3) SHT P-1 GENERAL NOTES #8 AIR CHAMBERS
 ARE NOT APPROVED. DELETE FROM NOTES.
 SECTION 604.9
 4) 61G1-16.004(2) FIRM LICENSE NUMBER IS
 REQUIRED. (6) PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT REQUIRED. FS
 481.2055.
  
  
 REVIEW BY KEN STEVENS