2004-11-04 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1) SHT P-1 SANITARY RISER DIAGRAM DOES |
| NOT MEET CODE REQUIREMENTS, NOR DOES IT |
| REFLECT THE FLOOR PLAN. |
| A) BAR SINK IN FAMILY ROOM NOT SHOWN ON |
| THE RISER DIAGRAM. SECTION 104.2.1 |
| B) VENT REQUIRED FOR EACH WASH MACHINE. |
| SECTION 901.2.1, AND THE WASH MACHINE |
| SHALL HAVE A CLEANOUT 4 FT. ABOVE THE |
| FLOOR FOR ACCESS. SECTION 708.10 |
| C) WASH MACHINE AND LAUNDRY SINK DO NOT |
| REFLECT THE FLOOR PLAN. THE W/M SHALL BE |
| ON THE RIGHT SIDE AND THE LAUNDRY SINK |
| SHALL BE ON THE LEFT SIDE. SECTION |
| 104.2.1 |
| D) KITCHEN PREP SINK IS MISLABLED AS A |
| BAR SINK. SECTION 104.2.1 |
| E) LAVS IN THE MASTER BATH TO BOTH FACE |
| INTO THE BATHROOM. SECTION 104.2.1 |
| F) BATHROOM #2 ALL FIXTURES SHALL LOOK |
| INTO THE SAME ROOM AS SHOWN ON THE FLOOR |
| PLAN. SECTION 104.2.1 |
| 2) INDICATE WHERE THE SHOWER ON THE |
| FLOOR PLAN OUTSIDE THE CABANA BATH |
| DRAINS TO. SECTION 104.2.1 |
| 3) SHT P-1 GENERAL NOTES #8 AIR CHAMBERS |
| ARE NOT APPROVED. DELETE FROM NOTES. |
| SECTION 604.9 |
| 4) 61G1-16.004(2) FIRM LICENSE NUMBER IS |
| REQUIRED. (6) PRINTED NAME OF THE PERSON |
| SEALING THE DOCUMENT REQUIRED. FS |
| 481.2055. |
| |
| |
| REVIEW BY KEN STEVENS |