Plan Review Notes For Permit 04100422 |
Permit Number |
04100422 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-10-28 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} PLEASE INDICATE THE LOCATION OF THE | | POOL PANEL ON THE PLAN AND INCLUDE SAME | | ON RISER PER 15.5. | | | | 2} PLEASE NOTE THAT AHU'S #2 & 3 DO NOT | | COMPLY WITH ATRICLE 424.3(B), OCP AND | | BRANCH CIRCUIT WIRING @ 125%. | | | | 3} PLEASE CLARIFY IF THE METER AND MAIN | | SHOWN ON THE RISER IS A COMBINATION UNIT | | AND SHOW LOCATION OF THE MAIN BREAKERS | | ON THE PLAN. | | | | 4} A SMOKE DETECTOR IS REQUIRED IN CLOSE | | PROXIMITY TO THE STAIRWELL ON THE FIRST | | FLOOR LEVEL PER 905.2.2 FBC. | | | | 5} PLEASE PROVIDE THE ARCHITECTURAL | | FIRMS LICENSE # IN THE TITLE BLOCK PER | | 61G1-16.004 FAC. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|