Plan Review Notes
Plan Review Notes For Permit 04100422
Permit Number 04100422
Review Stop E
Sequence Number 1
Notes
Date Text
2004-10-28 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE INDICATE THE LOCATION OF THE
 POOL PANEL ON THE PLAN AND INCLUDE SAME
 ON RISER PER 15.5.
  
 2} PLEASE NOTE THAT AHU'S #2 & 3 DO NOT
 COMPLY WITH ATRICLE 424.3(B), OCP AND
 BRANCH CIRCUIT WIRING @ 125%.
  
 3} PLEASE CLARIFY IF THE METER AND MAIN
 SHOWN ON THE RISER IS A COMBINATION UNIT
 AND SHOW LOCATION OF THE MAIN BREAKERS
 ON THE PLAN.
  
 4} A SMOKE DETECTOR IS REQUIRED IN CLOSE
 PROXIMITY TO THE STAIRWELL ON THE FIRST
 FLOOR LEVEL PER 905.2.2 FBC.
  
 5} PLEASE PROVIDE THE ARCHITECTURAL
 FIRMS LICENSE # IN THE TITLE BLOCK PER
 61G1-16.004 FAC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026