Plan Review Notes
Plan Review Notes For Permit 04100422
Permit Number 04100422
Review Stop B
Sequence Number 1
Notes
Date Text
2004-11-15 00:00:00DENIED
  
  
 1)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
  
 2)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) THE TITLE BLOCK IS MISSING
 INFORMATION. THE LICENSE NUMBER OF THE
 FIRM, AS WELL AS, THE PRINTED NAME AND
 LICENSE NUMBER OF THE ARCHITECT SIGNING
 AND SEALING THE DOCUMENT IS REQUIRED.
 SEE FAC 61G1-16.004.
  
 4) SPECIFY THE ATTIC ACCESS AT THE GUEST
 SUITE. SPECIFY MINIMUM SIZE. SEE FBC
 2309.6.
  
 5) SPECIFY ON THE PLANS THAT THE DESIGN
 IS FOR A VENTLESS ATTIC. MUST COMPLY
 WITH BCAB REQUIREMENTS (SEE ATTACHMENT).
  
 SUBMIT AFFIDAVIT FROM THE ROOFING
 MATERIAL/SYSTEM MANUFACTURER CERTIFYING
 USE OF THEIR PRODUCT OVER AN UNVENTED
 ATTIC SYSTEM.
  
 6) SUBMIT CALCULATIONS FOR THE EAST
 ELEVATION WHICH SHOW THAT THE WALL
 OPENINGS DO NOT EXCEED THE 20% OF WALL
 AREA ALLOWED BY FBC TABLE 600 BASED ON A
 DISTANCE OF 10' TO THE PROPERTY LINE.
  
  
 7) 1007.8.1 WINDERS SHALL HAVE A MINIMUM
 TREAD DEPTH OF 6" AT THE NARROWEST EDGE
 & SHALL HAVE A MINIMUM TREAD DEPTH OF
 11" AT A POINT 12" FROM THE NARROW EDGE.
 WINDERS SHALL BE PERMITTEDTO BE USED
 AS A COMPONENT IN MEANS OF EGRESS WITHIN
 A DWELLING UNIT. SPECIFY ON PLANS.
  
 8) THE CONDITIONED AREA LISTED ON SHEET
 AO OF THE PLANS (4077 SQFT) CONFLICTS
 WITH THE 4321 SQFT LISTED ON THE ENERGY
 CALCULATION FORM. PLEASE CORRECT.
  
 9) PROVIDE A SECTION AND DETAILS FOR THE
 TWO STORY CHIMNEY AT THE FAMILY
 ROOM/NICHE. SPECIFY THE FOUNDATION AND
 FOUNDATION REINFORCEMENT REQUIREMENTS ON
 SHEET S1.
  
 10) SPECIFY THE WINDLOAD PRESSURES FOR
 THE OVERHEAD GARAGE DOOR ON A4.
  
 11) THE STRUCTURAL PLANS ON S2 DO NOT
 SHOW THE POURED CONC. TIE BEAM AT THE
 CEILING AS SPECIFIED ON DETAIL 2 ON A9.
 PLEASE CLARIFY.
  
 12) SPECIFY THE LOCATION AND MATERIAL
 FOR THE DRAFTSTOP AT THE FLOOR/CEILING
 ASSEMBLY DIVIDING IT INTO AREAS OF NO
 MORE THAN 500 SQFT PER FBC 2305.2.2.
  
 13) SPECIFY THE FIREBLOCKING AT THE TOP
 AND BOTTOM OF STAIR RUNS REQUIRED BY FBC
 2305.1.4.
  
 14) PROVIDE GARAGE DOOR BUCK FASTENING
 DETAILS ON THE STRUCTURAL SHEETS AS
 INDICATED BY THE NOTE ON A13.
  
 15) THE SECTIONS ON A6 ARE MISLABELED AS
 A5. PLEASE CORRECT.
  
 16) SPECIFY THE ROOFING MATERIAL FOR THE
 FLAT PORTION OF THE UPPER ROOF INDICATED
 ON SHEET S3. PROVIDE A DETAIL OF THE
 TRANSITION OF ROOF COVERINGS FROM FLAT
 TO SLOPED ROOFS.
  
 17) PLEASE CLARIFY THE "?" DETAIL ON
 SHEET S3.
  
 18) FBC 2804.2.4 REQUIRES CHIMNEYS TO
 EXTEND 3' ABOVE HIGHEST POINT THEY PASS
 THROUGH THE ROOF AND AT LEAST 2' HIGHER
 THAN ANY PART OF THE ROOF OR BUILDING
 WITHIN 10' HORIZONTALLY.
  
 19) PROVIDE THE LISTING IFORMATION AND
 SPECIFICATIONS FOR THE GAS BBQ.
  
 20) SPECIFY THE SPECIAL ROOF SHEATHING
 NAILING REQUIREMENTS AND ZONES AS
 REQUIRED BY REVISED TABLE 2306.1 OF THE
 CITY OF WPB AMENDMENTS TO THE 2001 FBC.
  
 21) THE ROOF HEIGHT IS INCORRECTLY
 LABELED AS THE SECOND FLOOR PLATE HEIGHT
 ON A4.
  
 22) PROVIDE STATE OR LOCAL PRODUCT
 APPROVAL FOR THE CONSTRUCTION GLASS
 INDUSTRIES CORP. PRODUCTS. SEE RULE
 9B-72.(SEE LOCAL PRODUCT APPLICATION
 FORM ATTACHED)
  
 23) SUBMIT A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. SPECIFY
 THE MOUNT TYPE, FASTENERS & SPACING OF
 FASTENERS.
  
 24) SUBMIT PRODUCT APPROVAL FOR THE
 MAHOGANY DOOR WITH SIDELITES.
  
 25) PRODUCT APPROVAL WAS SUBMITTED FOR
 FIBERGLASS DOORS AND THE DOOR SCHEDULE
 CALLS FOR ALL EXTERIOR DOORS TO BE
 ALUMINUM CLAD OR MAHOGANY WOOD DOORS.
 PLEASE CLARIFY.
  