Plan Review Notes
Plan Review Notes For Permit 04100413
Permit Number 04100413
Review Stop E
Sequence Number 1
Notes
Date Text
2005-01-25 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1) LAUNDRY CIRCUIT LOAD. A LOAD OF NOT
 LESS THAN 1500 VOLT-AMPERES SHALL BE
 INCLUDED FOR EACH 2-WIRE LAUNDRY BRANCH
 CIRCUIT INSTALLED AS REQUIRED BY
 210.11(C)(2). THIS LOAD SHALL BE
 PERMITTED TO BE INCLUDED WITH THE
 GENERAL LIGHTING LOAD AND SUBJECTED TO
 THE DEMAND FACTORS PROVIDED IN TABLE
 220.11.
  
 2} 220.18 ELECTRIC CLOTHES DRYERS
 DWELLING UNIT(S).
 THE LOAD FOR HOUSEHOLD ELECTRIC CLOTHES
 DRYERS IN A DWELLING UNIT(S) SHALL BE
 5000 WATTS (VOLT-AMPERES) OR THE
 NAMEPLATE RATING, WHICHEVER IS LARGER,
 FOR EACH DRYER SERVED.
  
 3} 110.9 INTERRUPTING RATING.
 EQUIPMENT INTENDED TO INTERRUPT CURRENT
 AT FAULT LEVELS SHALL HAVE AN
 INTERRUPTING RATING SUFFICIENT FOR THE
 NOMINAL CIRCUIT VOLTAGE AND THE CURRENT
 THAT IS AVAILABLE AT THE LINE TERMINALS
 OF THE EQUIPMENT.
  
 4} THE LOCATION OF THE ELECTRICAL
 SERVICE EQUIPMENT IS IN VIOLATION OF
 ARTICLE 110.26 WITH RELATIONSHIP TO THE
 STEPS.
  
 6} SEE ARTICLE 210.52(E) FOR OUTSIDE
 RECEPTACLE REQUIREMENTS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  