| PLEASE MAKE THE FOLLOWING CORRECTIONS |
| FOR CODE COMPLIANCE AND RESUBMIT FOR |
| REVIEW. |
| |
| 1) LAUNDRY CIRCUIT LOAD. A LOAD OF NOT |
| LESS THAN 1500 VOLT-AMPERES SHALL BE |
| INCLUDED FOR EACH 2-WIRE LAUNDRY BRANCH |
| CIRCUIT INSTALLED AS REQUIRED BY |
| 210.11(C)(2). THIS LOAD SHALL BE |
| PERMITTED TO BE INCLUDED WITH THE |
| GENERAL LIGHTING LOAD AND SUBJECTED TO |
| THE DEMAND FACTORS PROVIDED IN TABLE |
| 220.11. |
| |
| 2} 220.18 ELECTRIC CLOTHES DRYERS |
| DWELLING UNIT(S). |
| THE LOAD FOR HOUSEHOLD ELECTRIC CLOTHES |
| DRYERS IN A DWELLING UNIT(S) SHALL BE |
| 5000 WATTS (VOLT-AMPERES) OR THE |
| NAMEPLATE RATING, WHICHEVER IS LARGER, |
| FOR EACH DRYER SERVED. |
| |
| 3} 110.9 INTERRUPTING RATING. |
| EQUIPMENT INTENDED TO INTERRUPT CURRENT |
| AT FAULT LEVELS SHALL HAVE AN |
| INTERRUPTING RATING SUFFICIENT FOR THE |
| NOMINAL CIRCUIT VOLTAGE AND THE CURRENT |
| THAT IS AVAILABLE AT THE LINE TERMINALS |
| OF THE EQUIPMENT. |
| |
| 4} THE LOCATION OF THE ELECTRICAL |
| SERVICE EQUIPMENT IS IN VIOLATION OF |
| ARTICLE 110.26 WITH RELATIONSHIP TO THE |
| STEPS. |
| |
| 6} SEE ARTICLE 210.52(E) FOR OUTSIDE |
| RECEPTACLE REQUIREMENTS. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| |