2004-10-20 00:00:00PROVISO:
 REMOTE CONDENSER LOCATED ON THE ROOF,
 SHALL COMPLY WITH 2001 FBC 1511.7 FOR
 CLEARANCE BETWEEN THE ROOF SURFACE AND
 THE BOTTOM OF THE SUPPORT RAIL.
  
 WIDTH OF MECHMINIMUM CLEARANCE
 UNITABOVE THE ROOF
 (INCHES)SURFACE (INCHES)
 ----------------------------------------
 < 2414
 24 < 36 18
 36 < 48 24
 48 < 60 30
 > 60 48
  