Plan Review Notes
Plan Review Notes For Permit 04100260
Permit Number 04100260
Review Stop M
Sequence Number 1
Notes
Date Text
2004-10-19 00:00:00PROVISO:
 RETURN TRANSFER GRILLES ARE TO BE A
 MINIMUM OF 50 SQ INCHES OF FREE AREA TO
 100 CFM OF SUPPLY AIR IN ACCORDANCE WITH
 2001 FBC(M) 601.4 EXCEPTION #2.
 BEDROOM #3 SHALL BE A MINIMUM OF 10"X8"
 BEDROOM #2 SHALL BE A MINIMUM OF 10"X10"
  
 PLEASE NOTE TRANSFER GRILLE INDICATED
 IN THE MASTER BATHROOM SHOULD BE
 RELOCATED TO AC#2 CLOSET.AIR FROM THE
 BATHROOM AREA IS NOT TO BE RECIRCULATED.
 2001 FBC(M) 402.3.1.
  
 AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  