Plan Review Notes For Permit 04100260 |
Permit Number |
04100260 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-10-19 00:00:00 | PROVISO: | | RETURN TRANSFER GRILLES ARE TO BE A | | MINIMUM OF 50 SQ INCHES OF FREE AREA TO | | 100 CFM OF SUPPLY AIR IN ACCORDANCE WITH | | 2001 FBC(M) 601.4 EXCEPTION #2. | | BEDROOM #3 SHALL BE A MINIMUM OF 10"X8" | | BEDROOM #2 SHALL BE A MINIMUM OF 10"X10" | | | | PLEASE NOTE TRANSFER GRILLE INDICATED | | IN THE MASTER BATHROOM SHOULD BE | | RELOCATED TO AC#2 CLOSET.AIR FROM THE | | BATHROOM AREA IS NOT TO BE RECIRCULATED. | | 2001 FBC(M) 402.3.1. | | | | AUXILIARY DRAIN PAN WITH OVERFLOW | | PROTECTION REQUIRED PER 2001 FBC(M) | | 307.2.3. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|