Plan Review Notes
Plan Review Notes For Permit 04100133
Permit Number 04100133
Review Stop E
Sequence Number 1
Notes
Date Text
2004-10-28 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THERE IS NO DISCONNECT SWITCH OR
 MEANS OF DISCONNECT SHOWN OR INDICATED.
 SEE ARTICLE 600.6 AND 600.6(A) NEC.
  
 2} THE ENGINEERS TITLE BLOCK "AGK,INC"
 REQUIRES THAT A CERTIFICATE OF
 AUTHORIZATION NUMBER BE INCLUDED PER
 61G15-23.002(2) FAC.PLEASE INCLUDE SAME
 ON RESUBMITTAL.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026