Date Text
2004-10-20 00:00:00**************DENIED********************
  
 1) WHEN THE FIRE ALARM CONTROL UNIT,
 INCLUDING THE DIALER-COMMUNICATOR, IS
 REPLACED IN AN EXISTING SYSTEM, IT WILL
 BE TREATED AS IF IT WERE A NEW SYSTEM.
  
 2) NEW FIRE ALARM SYSTEMS SHALL BE
 LISTED FOR CENTRAL STATION SERVICE.
  
 3) ALL NEW FIRE ALARM SYSTEMS THAT
 SUPERVISE FIRE SPRINKLER SYSTEMS SHALL
 BE UL CERTIFICATED AND HAVE DOCUMENT
 ATTESTING TO THIS CERTIFICATION PRIOR TO
 FINAL APPROVAL OF THE FIRE ALARM SYSTEM.
  
 4) THE FIRE ALARM SYSTEM SHALL BE
 CLASS "A" OR FULLY ADDRESSABLE.
  
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722