Plan Review Notes For Permit 04100051 |
Permit Number |
04100051 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-10-23 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | FBC-2001 CHAPTER 11 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | 1) SUBMIT DETAILS FOR THE ACCESSIBLE | | FIXTURES. THE TOILET ROOM PER SECTIONS | | 11-4.16, 11-4.19, & 11-4.22 AND ALL SUB- | | SECTIONS. THE DRINKING FOUNTAIN PER SEC- | | TION 11-4.15, AND ALL SUBSECTIONS. THE | | BREAK ROOM SINK PER SECTION 11-4.24 AND | | ALL SUBSECTIONS. | | 2) SUBMIT A SITE PLAN SHOWING LOCATION | | OF THE SEWER CONNECTION, THE WATER METER | | AND THE RPZ BACKFLOW. | | 3) FAC 6115-23.002 ALL PLANS SHALL BE | | SIGNED AND SEALED & DATED BY THE ENGIN- | | EER, COPINE ARE NOT ACCEPTABLE. ALSO ALL | | INFORMATION REQUIRED ON THE TITLE BLOCK | | SHALL BE SHOWN. FS 471.025 | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|