Plan Review Notes For Permit 04090888 |
Permit Number |
04090888 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2005-04-22 00:00:00 | PROVISO: | | FAN SHUTDOWN REQUIRED WITH NOTIFICATION | | TO ALARM/STROBE IN NORMALLY OCCUPIED | | AREAS.2001 FBC/M 606.2.1 & 606.4.1 #2. | | | | PLEASE NOTE OUTSIDE AIR LOCATED A | | MINIMUM OF 10 FT FROM NOXIOUS | | CONTAMINANT I.E., STREETS, ALLEYS, | | PARKING LOTS, PLUMBING OR EXHAUST VENTS. | | 2001 FBC/M 401.5.1. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|