Plan Review Notes
Plan Review Notes For Permit 04090888
Permit Number 04090888
Review Stop M
Sequence Number 1
Notes
Date Text
2004-10-05 00:00:00DENIED:
 PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER 2001 FBC(M) 403.3.INDICATE
 FRESH AIR INTAKE, DUCT SIZE AND MATERIAL
 ON PLAN.
  
 PROVIDE SUBMITTAL ON THE CONDESING UNIT
 STANDS.PLEASE NOTE, PER 2001 FBC(M)
 306.5 PERMANENT MEANS OF ACCESS REQUIRED
 WHERE ROOF HEIGHT EXCEEDS 16 FT.
  