 THE LOAD CALCULATIONS SUBMITTED MUST BE
 CORRECTED AS FOLLOWS.
  
 1} THE PLANS MUST CONTAIN THE PRINTED AN
 SIGNED NAME OF THE DESIGNER OF RECORD
 PER 104.2.1 FBC.
  
 2} THE GENERAL LIGHTING LOAD IS LISTED @
 6600 AND THEN A CALULATION OF 3 WATTS
 PER SQUARE FOOT IS SHOWN, WHICH WOULD BE
 THE GENERAL LIGHTING LOAD, @ 3000.
 PLEASE CORRELATE.
  
 3} THE SMALL APPLIANCE LOAD MUST COMPLY
 WITH 220.16, 2@ 1500=3000WATTS MINIMUM.
  
 4} THE WASHER IS INCORRECTLY CALCULATED
 AT 10000 WATTS, BUT MUST BE A MINIMUM OF
 1500 WATTS IF REFERRING TO THE LAUNDRY
 LOAD REQUIREMENT.
  
 5} A/C #1&2 ARE SHOWN AS 5000 EACH, AND
 SHOWN AGAIN AT 15000 AND 10000. PLEASE
 CORRELATE.
  
 6} THE RANGE MUST BE CALCULATED PER
 220.19.
  
 7} CLARIFY "HWIT" ON CALC.
  
 8} THE POOL PUMP AND HEATER MUST BE
 CALCULATED AT 125%. SEE ARTICLES 424 &
 430.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  