2004-10-08 00:00:00DENIED:
 1.PLAN SHEET 7 OF 7 CONDENSING UNIT
 DETAIL, PLEASE PROVIDE THE FOLLOWING:
 - DETAIL OF THE ATTACHMENT TO THE ROOF.
 - INDICATE DEMENSION BEWTEEN THE ROOF
 SURFACE AND THE BOTTOM OF THE SUPPORT
 RAIL, REFERENCE 2001 FBC 1511.7.
  
 2.PLEASE CLARIFY OUTSIDE AIR
 CALCULATIONS.PLAN DOES NOT INDICATE
 OUTSIDE AIR INTAKE OR DUCTWORK.IS
 THIS EXISTING?
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.