Date |
Text |
2004-10-22 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 04090836 |
| ADD: 1400 CENTREPARK DR # 10TH FL |
| CONT: PASS INTERNATIONAL |
| TEL: (561)239-0125 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1STREVIEW |
| ACTION: DENIED |
| |
| 1) PROVIDE THE SUITE NUMBER WHERE WORK |
| WILL BE COMPLETED UNDER THIS PERMIT. |
| |
| 2) PROVIDE NOC RECORDED WITH THE CLERK |
| OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| |
| 3) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| STOP PARTITIONS, HORIZONTAL EXIT PART- |
| ITIONS, EXIT ENCLOSURES, AND FIRE |
| RATED WALLS REQUIRED TO HAVE PROTECTED |
| OPENINGS SHALL BE EFFECTIVELY AND |
| PERMANETLY IDENTIFIED WITH SIGNS OR |
| STENCILING IN A MANNER ACCEPTABLE TO THE |
| AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| CEILING CEILING AND IN CONCEALED SPACES. |
| SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| PROTECT ALL OPENINGS". |
| |
| 4) PLANS INDICATE IN THE LEGOND SHEET 1, |
| 1 HR WALL AT STAIRWELL, TABLE 705.2.1. |
| REQUIRES A 2HR WALL AT STAIRWAYS ( SHAFT |
| CONSTRUCTION OVER 4 STORIES). |
| |
| 5) PLANS DO NOT INDICATE THAT THIS BUILD |
| ING IS FIRE SPRINKLERED,DOOR 1 AND 12 |
| DO NOT MEET THE REQUIREMENTS OF: |
| 1004.1.4 WHERE 2 OR MORE EXITS OR |
| EXIT ACCESS DOORS ARE REQUIED, AT LEAST |
| 2 OF THE EXIT OR EXIT ACCESS DOORS SHALL |
| BE PLACED A DISTANCE APART EQUAL TO NOT |
| LESS THAN 1/2 OF THE LENGTH OF THE MAX- |
| IMUM OVERALL DIAGONAL DIMENSION OF THE |
| BUILDING OR AREA TO BE SERVED. |
| |
| 6) SHEET 2 DETAIL 2 PROVIDE THE RATED |
| WALL ASSEMBLY NUMBER FOR 1 HR RATING, |
| EITHER UL, GYPSUM, ETC... |
| |
| 7)DOOR SCHEDULE, DOOR# 1/12 ARE EXISTING |
| RATED DOORS, BUT NOT NOTATION AS TO |
| DOOR CLOSURE. 705.1.3.5 FIRE DOORS SHALL |
| BE EQUIPPED WITH AN APPROVED CLOER. |
| |
| 8) TABLE 803.3 MINIMUM INTERIOR FINISH |
| CLASSIFICATION; PROVIDE INFORMATION |
| BASED ON INTERIOR FINISH REQUIREMENTS |
| BASED ON OCCUPANCY |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| THE PLANS WHEN RESUBMITTING PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN |
| BE FOUND, WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| JIM WITMER |
| BUILDING PLAN REVIEW |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |