Plan Review Notes
Plan Review Notes For Permit 04090836
Permit Number 04090836
Review Stop B
Sequence Number 1
Notes
Date Text
2004-10-22 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04090836
 ADD: 1400 CENTREPARK DR # 10TH FL
 CONT: PASS INTERNATIONAL
 TEL: (561)239-0125
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1) PROVIDE THE SUITE NUMBER WHERE WORK
 WILL BE COMPLETED UNDER THIS PERMIT.
  
 2) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 3) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 4) PLANS INDICATE IN THE LEGOND SHEET 1,
 1 HR WALL AT STAIRWELL, TABLE 705.2.1.
 REQUIRES A 2HR WALL AT STAIRWAYS ( SHAFT
 CONSTRUCTION OVER 4 STORIES).
  
 5) PLANS DO NOT INDICATE THAT THIS BUILD
 ING IS FIRE SPRINKLERED,DOOR 1 AND 12
 DO NOT MEET THE REQUIREMENTS OF:
 1004.1.4 WHERE 2 OR MORE EXITS OR
 EXIT ACCESS DOORS ARE REQUIED, AT LEAST
 2 OF THE EXIT OR EXIT ACCESS DOORS SHALL
 BE PLACED A DISTANCE APART EQUAL TO NOT
 LESS THAN 1/2 OF THE LENGTH OF THE MAX-
 IMUM OVERALL DIAGONAL DIMENSION OF THE
 BUILDING OR AREA TO BE SERVED.
  
 6) SHEET 2 DETAIL 2 PROVIDE THE RATED
 WALL ASSEMBLY NUMBER FOR 1 HR RATING,
 EITHER UL, GYPSUM, ETC...
  
 7)DOOR SCHEDULE, DOOR# 1/12 ARE EXISTING
 RATED DOORS, BUT NOT NOTATION AS TO
 DOOR CLOSURE. 705.1.3.5 FIRE DOORS SHALL
 BE EQUIPPED WITH AN APPROVED CLOER.
  
 8) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved