Plan Review Notes
Plan Review Notes For Permit 04090793
Permit Number 04090793
Review Stop P
Sequence Number 3
Notes
Date Text
2005-01-19 00:00:00DENIED;
 1.FOUNTAIN SHOULD BE PERMITED
 SEPURATLY.
 2.SHOW DETAIL OF WATER HEATER. THERMAL
 EXPANSION CONTROL REQUIRED PER FBC
 PLUMBING SEC. 607.3.
 3.WATER ISOMETRIC, SHOCK ARRESTORS TO BE
 INSTALLED PER SEC.604.9. NOT NEEDED ON
 LAVS, SHR. AND TUBS.
 4.DETAIL FOR EMPLOYEE BATHROOM AND BREAK
 SINK SHOULD BE TRANSFURED FROM 8X11 SHT.
 AND 8X17 SHT.TO NEW PLUMBING PAGE.
 5.MODEL BATHROOM AND KITCHEN. SHOW
 COMPLIANCE TO THE FAIR HOUSING ACT.SHOW
 CLEAR FLOOR SPACE AND DETAILS FOR
 REQUIRED BACKING.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  