Plan Review Notes For Permit 04090769 |
Permit Number |
04090769 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-11-15 00:00:00 | ********* UNSAT ********* | | | | 1)NOTE: PLEASE SEE NOTE #1 FROM FIRST | | REVIEW. | | PLEASE CORRELATE LOAD ON LOAD | | CALCULATIONS AND LOAD/KW RATING OF HEAT | | PUMP ON SPEC SHEETS. LOAD ON LOAD CALCS | | INDICATE 4.5KW? | | NEW HEAT PUMP SPEC SHEET SHOWS ARE | | LARGER UNIT THAN ON PREVIOUS SUBMITTAL. | | PLEASE SEE ALL CONTINUOUS LOADS | | (HEAT-PUMP)ARE TO BE SHOWN AT 125% ALONG | | WITH MOTOR LOADS. | | 215.3,230.42 ETC. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|