Plan Review Notes
Plan Review Notes For Permit 04090769
Permit Number 04090769
Review Stop E
Sequence Number 1
Notes
Date Text
2004-10-05 00:00:00********* UNSAT ************
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM/
 LOAD CALCULATIONS AND SPEC SHEET FOR
 HEAT PUMP AND OCP.
  
 SHOWS 2P-25A ON LOAD CALCS, A 2P60A ON
 SPEC SHEET AND A 2P40A ON PLANS??
 PLEASE SEE MIN LOAD ALSO TO BE FIGURED
 @125% FOR CONTINUOUS LOAD OF 3 OR MORE
 HOURS. POOL PUMP ALSO.
  
 2)NOTE: PLEASE SEE WIRING DIAGRAM SHOWS
 A NEW 200A PANEL. PLEASE CLARIFY FEED,
 #OF CONDUCTORS, CONDUIT ETC
 215.5
  
 3)NOTE: PLEASE SEE LOAD FOR A/C,OCP ETC
 424.3B
 PLEASE SEE 220.31B FOR EXISTING DWELLING
 -S. A/C AT 100%.
 PLEASE SEE MISSING SMALL APPLIANCE
 CIRCUITS PER 220.16, 210.11 ETC
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]