Plan Review Notes
Plan Review Notes For Permit 04090723
Permit Number 04090723
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-10-06 00:00:00***********DENIED***********************
  
 1) PLEASE SUBMIT SHOP DRAWINGS AND CUT
 SHEETS SHOWING LOCATION OF THE FACP.
  
 2) WHEN THE FIRE ALARM CONTROL UNIT,
 INCLUDING THE DIALER-COMMUNICATOR, IS
 REPLACED IN AN EXISTING SYSTEM, IT WILL
 BE TREATED AS IF IT WERE A NEW SYSTEM.
  
 3) IS THIS BUILDING FIRE SPRINKLER
 PROTECTED? PLEASE BE AWARE THAT ALL NEW
 FIRE ALARM SYSTEMS THAT SUPERVISE FIRE
 SPRINKLER SYSTEMS SHALL BE UL
 CERTIFICATED AND HAVE DOCUMENT ATTESTING
 TO THIS CERTIFICATION PRIOR TO FINAL
 APPROVAL OF THE FIRE ALARM SYSTEM.
  
 4) THE FIRE ALARM SYSTEM SHALL BE
 CLASS "A" OR FULLY ADDRESSABLE.
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722