Plan Review Notes
Plan Review Notes For Permit 04090711
Permit Number 04090711
Review Stop E
Sequence Number 2
Notes
Date Text
2005-10-09 00:00:00********* UNSAT **********
  
 1)NOTE: PLEASE SEE REAR PORCH IS SHOWING
 A J-BOX FOR POSSIBLE FUTURE FAN/LT.
 PLEASE SEE 210.70 LS 1015.8 WHICH
 REQUIRES A LT FIXTURE OF SOME SORT FOR
 MEANS OF EGRESS.
  
 2)NOTE: PLEASE SEE LOAD CALCULATIONS FOR
 EACH PANEL ARE NOT COMPLETE AND ARE
 SHOWN WITH "0" LOAD ON EACH PANEL.
 PLEASE CORRECT, AND SHOW LOAD CALCS, AND
 LOAD ON EACH PANEL.
 215.5,220
  
 3)NOTE: PLEASE SEE PLANS FOR ALL
 LOCATIONS WHICH INDICATE A PRE-WIRE FOR
 "SD'S".
 PLEASE SEE THIS SEEMS TO BE A MISPRINT
 AS "SD" IS FOR THE SMOKE DETECTORS AND
 THIS SHOULD BE "SP" FOR SPEAKER
 PRE-WIRE, IF INDEED THIS IS WHAT IS
 MEANT.
  
 4)NOTE: PLEASE SEE SMOKE DETECTORS ARE
 BEING SHOWN CIRCUITED TO "A-20" , WHICH
 PANEL SCHEDULE SHOWS THIS AS THE SMALL
 APPLIANCE CIRCUIT.
 PLEASE SEE CIRCUIT A-20 IS ALSO BEING
 SHOWN ON PLANS FOR SMALL APPL.
 PLEASE SEE 210.52B1,210.11C1 WHICH DOES
 NOT PERMIT ANY OTHER DEVICES EXCEPT
 THOSE ALLOWED PER ABOVE.
 PLEASE ALSO SEE NOTES TO ELECTRICAL
 PLANS MENTIONS ONLY THOSE CIRCUITS
 LISTED TO BE "ARC-FAULT PROTECTED" ,
 HOWEVER UNDER THE 2002 NEC 210.12, "ALL
 OUTLETS" BRANCH CIRCUITS" FOR BEDRMS ARE
 REQUIRED TO BE PROTECTED.
 PLEASE SEE NUMEROUS CIRCUITS AS NOTED DO
 NOT CORRELATE WITH PLANS OR PANEL
 SCHEDULES/
 PLEASE SEE ARC FAULT PROTECTION LISTED
 FOR SM APPL, OVEN, A/C ETC,
 PLEASE CORRELATE ALL.
  
 5)NOTE: PLEASE SEE BATH RM SHOWING
 CIRCUIT B-10, WHICH IS FOR ENTRY. THE
 BATH RM CIRCUITING SHALL BE PER
 210.52D,210.11C3. IN EITHER CASE A
 RECEPT CIRCUIT MUST BE 20A AND #12.
  
 6)NOTE: PLEASE SEE PANEL "B" IS BEING
 SHOWN AT TWO LOCATIONS ON PLANS???
 PLEASE ADJUST.
  
 7)NOTE: PLEASE KNOW, ALL "OPTIONAL"
 ITEMS SHALL BE SHOWN AS INSTALLED OR NOT
 INSTALLED IF NOT REQUIRED.
 OPTIONS MAY BE SHOWN ON ORIGINAL PLANS
 FOR PERMITTING, HOWEVER ALL
 OPTIONS/REVISIONS ARE TO BE SUBMITTED
 FOR REVIEW BEFORE ROUGH ELECTRICAL
 INSPECTION.
  
 8)NOTE: PLEASE SEE NOTES PERTAINING TO
 AIC RATINGS OF MAINS TO BE USED.
 PLEASE CLARIFY NOTE, AS IT DOES NOT SEEM
 TO CONTAIN INFORMATION FOR LENGTHS
 BETWEEN 70-80 FT.???
 PLEASE ADJUST.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.