Date |
Text |
2005-10-09 00:00:00 | ********* UNSAT ********** |
| |
| 1)NOTE: PLEASE SEE REAR PORCH IS SHOWING |
| A J-BOX FOR POSSIBLE FUTURE FAN/LT. |
| PLEASE SEE 210.70 LS 1015.8 WHICH |
| REQUIRES A LT FIXTURE OF SOME SORT FOR |
| MEANS OF EGRESS. |
| |
| 2)NOTE: PLEASE SEE LOAD CALCULATIONS FOR |
| EACH PANEL ARE NOT COMPLETE AND ARE |
| SHOWN WITH "0" LOAD ON EACH PANEL. |
| PLEASE CORRECT, AND SHOW LOAD CALCS, AND |
| LOAD ON EACH PANEL. |
| 215.5,220 |
| |
| 3)NOTE: PLEASE SEE PLANS FOR ALL |
| LOCATIONS WHICH INDICATE A PRE-WIRE FOR |
| "SD'S". |
| PLEASE SEE THIS SEEMS TO BE A MISPRINT |
| AS "SD" IS FOR THE SMOKE DETECTORS AND |
| THIS SHOULD BE "SP" FOR SPEAKER |
| PRE-WIRE, IF INDEED THIS IS WHAT IS |
| MEANT. |
| |
| 4)NOTE: PLEASE SEE SMOKE DETECTORS ARE |
| BEING SHOWN CIRCUITED TO "A-20" , WHICH |
| PANEL SCHEDULE SHOWS THIS AS THE SMALL |
| APPLIANCE CIRCUIT. |
| PLEASE SEE CIRCUIT A-20 IS ALSO BEING |
| SHOWN ON PLANS FOR SMALL APPL. |
| PLEASE SEE 210.52B1,210.11C1 WHICH DOES |
| NOT PERMIT ANY OTHER DEVICES EXCEPT |
| THOSE ALLOWED PER ABOVE. |
| PLEASE ALSO SEE NOTES TO ELECTRICAL |
| PLANS MENTIONS ONLY THOSE CIRCUITS |
| LISTED TO BE "ARC-FAULT PROTECTED" , |
| HOWEVER UNDER THE 2002 NEC 210.12, "ALL |
| OUTLETS" BRANCH CIRCUITS" FOR BEDRMS ARE |
| REQUIRED TO BE PROTECTED. |
| PLEASE SEE NUMEROUS CIRCUITS AS NOTED DO |
| NOT CORRELATE WITH PLANS OR PANEL |
| SCHEDULES/ |
| PLEASE SEE ARC FAULT PROTECTION LISTED |
| FOR SM APPL, OVEN, A/C ETC, |
| PLEASE CORRELATE ALL. |
| |
| 5)NOTE: PLEASE SEE BATH RM SHOWING |
| CIRCUIT B-10, WHICH IS FOR ENTRY. THE |
| BATH RM CIRCUITING SHALL BE PER |
| 210.52D,210.11C3. IN EITHER CASE A |
| RECEPT CIRCUIT MUST BE 20A AND #12. |
| |
| 6)NOTE: PLEASE SEE PANEL "B" IS BEING |
| SHOWN AT TWO LOCATIONS ON PLANS??? |
| PLEASE ADJUST. |
| |
| 7)NOTE: PLEASE KNOW, ALL "OPTIONAL" |
| ITEMS SHALL BE SHOWN AS INSTALLED OR NOT |
| INSTALLED IF NOT REQUIRED. |
| OPTIONS MAY BE SHOWN ON ORIGINAL PLANS |
| FOR PERMITTING, HOWEVER ALL |
| OPTIONS/REVISIONS ARE TO BE SUBMITTED |
| FOR REVIEW BEFORE ROUGH ELECTRICAL |
| INSPECTION. |
| |
| 8)NOTE: PLEASE SEE NOTES PERTAINING TO |
| AIC RATINGS OF MAINS TO BE USED. |
| PLEASE CLARIFY NOTE, AS IT DOES NOT SEEM |
| TO CONTAIN INFORMATION FOR LENGTHS |
| BETWEEN 70-80 FT.??? |
| PLEASE ADJUST. |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW. |