2004-11-05 00:00:00 | DENIED |
| |
| 1) THE SURVEY HAS THE WRONG STREET |
| NAME. |
| SUBMIT CORRECTED SURVEY SHOWING THE LOT |
| ON FOX HOLLOW DRIVE. |
| |
| 2) THE PRINTED NAME OF THE PERSON |
| SEALING THE PLAN IS REQUIRED TO BE ON |
| THE PLAN. SEE F.A.C.61G1-16.004. |
| |
| 3) PLANS ARE REQUIRED TO BE PERSONALLY |
| SIGNED BY THE RESPONSIBLE ARCHITECT PER |
| F.A.C.61G1-16.003. IF THE SIGNATURE ON |
| THE PLANS IS THE ARCHITECT'S LEGAL |
| SIGNATURE, PLEASE SUBMIT A SIGNED AND |
| SEALED LETTER STATING THIS FOR OUR |
| FILES. |
| |
| 4) ON SHEET A1 THE SECTION AT THE |
| WINDOWS IN THE MASTER BEDROOM IS |
| LABELED |
| B ON A5 AND THERE IS NO SUCH SECTION ON |
| A5. PLEASE CORRECT. |
| |
| 5) ON SHEET A1 THE ID TAG FOR THE |
| COLUMN |
| IN THE LIVING ROOM IS IN THE WRONG |
| LOCATION. PLEASE CORRECT. |
| |
| 6) THE DOOR SCHEDULE ON A2 SPECIFIES |
| (2) |
| 3'X 8' DOORS AT THE ENTRY AND THE FLOOR |
| PLAN ON A1 SPECIFIES A SINGLE DOOR WITH |
| A SIDELITE. |
| |
| 7) THE WINDOWS (K) IN THE MASTER BATH |
| AND BATH #2 ARE REQUIRED TO BE SAFEETY |
| GLASS PER FBC 2405.2. |
| |
| 8) THE GLASS BLOCK ON THE ZERO LOT LINE |
| ARE REQUIRED TO BE ONE HOUR FIRE RATED. |
| PLEASE SPECIFY THIS ON THE PLANS. |
| |
| 9) THE GLASS BLOCK HAS THE WRONG ID TAG |
| AND DOES NOT CORRESPOND TO THE |
| SCHEDULE. |
| |
| 10) ONE OF THE SECTIONS ON A2 IS |
| MISLABELED. IT SHOULD BE A ON A5. |
| |
| 11) ON SHEET S1 DETAIL MARKS (9) AT THE |
| MASTER BATH, (10) AT THE LIVING ROOM |
| AND |
| (5) AT THE GARAGE ARE IN THE WRONG |
| LOCATIONS. PLEASE CORRECT. |
| |
| 12) ON SHEET A2 THE EXTERIOR WALL AT |
| BEDROOM #4 IS INCORRECTLY IDENTIFIED AS |
| WOOD FRAME BY NOTE #25 ON A1. PLEASE |
| CORRECT. |
| |
| 13) REVISE THE BUCK NOTES ON A6. FBC |
| 1707.4.4.2 REQUIRES WINDOW AND DOOR |
| ASSEMBLIES TO BE ANCHORED THROUGH 1X |
| BUCKS INTO THE SUBSTRATE. |
| |
| 14) SPECIFY THE BOTTOM CORD LIVE LOAD |
| FOR THE ROOF TRUSSES ON S3. FBC TABLE |
| 1604.1 REQUIRES A MINIMUM LIVE LOAD OF |
| 10PSF FOR ATTICS WITHOUT STORAGE. |
| |
| 15) REVISE THE WIND SPEED ON SHEET S3. |
| THE CITY OF WPB IS IN THE 140 MPH WIND |
| ZONE. |
| |
| 16) SPECIFY THE FLORIDA PRODUCT |
| APPROVAL |
| # (FL 599)FOR THE NUVUE CONNECTOR IN |
| THE |
| SCHEDULE ON S3. |
| |
| 17) THE PLANS SHOW AN ELECTRIC WATER |
| HEATER AND THE ENERGY CALC. FORM |
| SPECIFIES A GAS WATER HEATER. PLEASE |
| CORRECT. |
| |
| 18) SPECIFY THE POSITIVE AND NEGATIVE |
| WIND LOAD PRESSURES FOR THE TWO |
| OVERHEAD |
| GARAGE DOORS. |
| |
| 19) SUBMIT A KEY PLAN AND AN |
| INSTALLATION SCHEDULE INDICATING WHICH |
| OPENINGS WILL BE SHUTTERED. SPECIFY THE |
| TYPE OF MOUNTING, FASTENERS AND SPACING |
| THAT WILL BE USED. |
| |
| 20) SUBMIT THE INSTALLATION |
| INSTRUCTIONS |
| FROM MASONITE INTERNATIONAL FOR THE |
| SINGLE OUTSWING EXTERIOR DOOR WITH ONE |
| SIDELITE ENTRY DOOR AS SHOWN ON THE |
| PLANS. |
| |