Plan Review Notes For Permit 04090582 |
Permit Number |
04090582 |
|
Review Stop |
E |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2007-03-06 12:17:23 | | | | | REVISION DENIED | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | THE WIRE SIZE AND OCPDO NOT COMPLY WITH 240 OR | | 310.16, OR BOTH IN THE FOLLOWING: | | 1} CIRCUIT 1&3,5&7, AND 9&11 PANEL "A". | | 2} CIRCUITS 2&4 PANEL"C". | | | | ALTHOUGH #6 CONDUCTORS ON A 30 AMP OCP ARE NOT A | | VIOLATION, THEY WILL NOT PHYSICALLY FIT ON THE BREAKER. | | AND MUST BE INSTALLED PER PLAN, OR CHANGE THE PLAN TO | | INDICATE ACTUAL CONDITIONS. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|