Plan Review Notes
Plan Review Notes For Permit 04090582
Permit Number 04090582
Review Stop P
Sequence Number 1
Notes
Date Text
2004-10-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT A4 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT
 MEET CODE REQUIREMENTS.
 A) A STANDPIPE IS REQUIRED FOR THE WASH
 MACHINE. SECTION 1002.1 & 802.4 - THE
 CLEANOUT FOR THE WASH MACHINE SHALL BE
 LOCATED 4' ABOVE THE FLOOR FOR ACCESS.
 SECTION 708.10.
 B) THE MASTER BATH SHOWS ONE LAV ON THE
 FLOOR PLAN, BUT SHOWS TWO ON THE SANIT-
 ARY RISER DIAGRAM. CORRELATE RISER WITH
 FLOOR PLAN. SECTION 104.2.1.
 C) THE MASTER BATH FLOOR PLAN SHOWS THE
 BIDET UPSTREAM OF THE WATER CLOSET ON
 THE SAME WALL BUT THE RISER DIAGRAM
 SHOWS THE BIDET BETWEEN THE W/C AND THE
 LAV. SECTION 104.2.1
 D) FLOOR PLAN FOR BATH #2 SHOWS A SHOW-
 ER, BUT THE RISER DIAGRAM SHOWS A TUB.
 PLEASE CORRELATE RISER WITH THE FLOOR
 PLAN. SECTION 104.2.1.
 E) SUMMER KITCHEN SINK SHALL DISCHARGE
 DOWNSTREAM OF THE HORIZONTAL WET VENT
 FOR THE CABANA BATHROOM FIXTURES. SECT-
 ION 909.1
  
 REVIEW BY KEN STEVENS