Plan Review Notes For Permit 04090582 |
Permit Number |
04090582 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-10-21 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | | | 1) SHT A4 SANITARY RISER DIAGRAM DOES | | NOT REFLECT THE FLOOR PLAN, NOR DOES IT | | MEET CODE REQUIREMENTS. | | A) A STANDPIPE IS REQUIRED FOR THE WASH | | MACHINE. SECTION 1002.1 & 802.4 - THE | | CLEANOUT FOR THE WASH MACHINE SHALL BE | | LOCATED 4' ABOVE THE FLOOR FOR ACCESS. | | SECTION 708.10. | | B) THE MASTER BATH SHOWS ONE LAV ON THE | | FLOOR PLAN, BUT SHOWS TWO ON THE SANIT- | | ARY RISER DIAGRAM. CORRELATE RISER WITH | | FLOOR PLAN. SECTION 104.2.1. | | C) THE MASTER BATH FLOOR PLAN SHOWS THE | | BIDET UPSTREAM OF THE WATER CLOSET ON | | THE SAME WALL BUT THE RISER DIAGRAM | | SHOWS THE BIDET BETWEEN THE W/C AND THE | | LAV. SECTION 104.2.1 | | D) FLOOR PLAN FOR BATH #2 SHOWS A SHOW- | | ER, BUT THE RISER DIAGRAM SHOWS A TUB. | | PLEASE CORRELATE RISER WITH THE FLOOR | | PLAN. SECTION 104.2.1. | | E) SUMMER KITCHEN SINK SHALL DISCHARGE | | DOWNSTREAM OF THE HORIZONTAL WET VENT | | FOR THE CABANA BATHROOM FIXTURES. SECT- | | ION 909.1 | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|