Plan Review Notes
Plan Review Notes For Permit 04090278
Permit Number 04090278
Review Stop P
Sequence Number 1
Notes
Date Text
2004-10-09 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SUBMIT A DETAIL FOR BREAK AREA SINK
 SHOWING KNEE CLEARANCE 11-4.24.3, SINK
 DEPTH 11-4.24.4, CLEAR FLOOR SPACE WHICH
 SHALL BE PROVIDED IN FRONT OF A SINK TO
 ALLOW FORWARD APPROACH 11-4.24.5, & EX-
 POSED PIPES AND SURFACES 11-4.24.6
 2) SUBMIT MANUF. SPECIFICATIONS FOR PUMP
 SECTION 104.2.1
 3) SUBMIT A WATER RISER DIAGRAM SHOWING
 PIPE SIZES AND VALVE REQUIRED BY SECTION
 606.1(4). SECTION 104.3.1.1
  