Plan Review Notes For Permit 04090107 |
Permit Number |
04090107 |
|
Review Stop |
E |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2006-03-24 00:00:00 | | | THE GENERATOR ADDED TO THE RISER DIAGRAM | | MUST BE APPLIED FOR ON A SEPARATE | | PERMIT. | | | | THE REQUIREMENTS FOR A RESIDENTIAL | | GENERATOR PERMIT APPLICATIION ARE IN THE | | PACKAGE. | | | | AFTER THE GENERATOR PERMIT IS ISSUED THE | | RISER FOR THESE PLANS WILL HAVE TO BE | | RESUBMITTED TO SHOW THE CHANGES. | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} THE CIRCUIT NUMBERS AT THE DEVICES DO | | NOT MATCH THE PANEL SCHEDULES. INDICATE | | PANEL DESIGNATION WITH THE BRANCH | | CIRCUIT NUMBER, EG: A-33, EM-2 ETC. | | | | 2} THE PANELS IN THE UTILITY ROOM ARE IN | | VIOLATION OF 110.26 CLEARANCE | | REQUIREMENTS. | | | | 3} A RECEPTACLE NEEDS TO BE ADDED IN THE | | MASTER BEDROOM TO COMPLY WITH 210.52(A) | | SINCE THE CLOSET HAS BEEN REMOVED. | | | | 4} THE TOTAL DEMAND OF THE TWO PANELS | | EXCEEDS THE SIZE OF THE SERVICE AND | | LEAVES NO ROOM FOR FUTURE EXPANSION. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|