Date |
Text |
2004-10-08 00:00:00 | |
| PLEASE MAKE THE FOLLOWING CORRECTIONS |
| FOR CODE COMPLIANCE AND RESUBMIT FOR |
| REVIEW. |
| |
| 1} THE LAUNDRY CIRCUIT MUST BE |
| CALCULATED PER 220.16 (B), SEE CIRCUIT |
| #6, 1500VA. |
| |
| 2} PLEASE SEE THAT KITCHEN COUNTERTOP |
| RECEPTACLE SPACING DOES NOT APPEAR TO |
| COMPLY WITH 210.11(C)(1) SPACING |
| REQUIREMENTS. THE DISHWASHER RECEPTACLE |
| WOULD NOT BE INCLUDED IN THE SPACING AS |
| IT IS DEDICATED AND BELOW THE COUNTER, |
| ADD ONE ABOVE. ALSO SEE REVIEWED PLAN |
| FOR REDLINED AREAS. |
| |
| 3} PLEASE SHOW THE LOCATION OF THE NEW |
| 200 AMP DISCONNECT ON THE PLAN. |
| |
| 4} THE LIGHTING AND SMOKE DETECTOR |
| WIRING IN BEDROOMS MUST ALSO COMPLY |
| WITH 210.12. THE TERM "RECEPTACLE" HAS |
| BEEN REPLACED WITH "OUTLETS" IN THE |
| 2002 NEC. BY DEFINITION ALL ELECTRICAL |
| DEVICES WOULD BE INCLUDED UNDER THAT |
| ARTICLE. |
| |
| 5} THE ARCHITECT MUST SIGN THE PLANS |
| NOT RUBBER STAMP HIS NAME, PER |
| 61G1-16.003 FLORIDA ADMINISTRATIVE |
| CODE, AND IS ENFORCED BY THIS |
| DEPARTMENT. DO NOT SUBMIT PLANS IN |
| VIOLATION OF THIS ARTICLE. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLAN REVIEW |
| 561/805-6718 |
| [email protected] |
| FAX/:561/659-8026 |