 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE LAUNDRY CIRCUIT MUST BE
 CALCULATED PER 220.16 (B), SEE CIRCUIT
 #6, 1500VA.
  
 2} PLEASE SEE THAT KITCHEN COUNTERTOP
 RECEPTACLE SPACING DOES NOT APPEAR TO
 COMPLY WITH 210.11(C)(1) SPACING
 REQUIREMENTS. THE DISHWASHER RECEPTACLE
 WOULD NOT BE INCLUDED IN THE SPACING AS
 IT IS DEDICATED AND BELOW THE COUNTER,
 ADD ONE ABOVE. ALSO SEE REVIEWED PLAN
 FOR REDLINED AREAS.
  
 3} PLEASE SHOW THE LOCATION OF THE NEW
 200 AMP DISCONNECT ON THE PLAN.
  
 4} THE LIGHTING AND SMOKE DETECTOR
 WIRING IN BEDROOMS MUST ALSO COMPLY
 WITH 210.12. THE TERM "RECEPTACLE" HAS
 BEEN REPLACED WITH "OUTLETS" IN THE
 2002 NEC. BY DEFINITION ALL ELECTRICAL
 DEVICES WOULD BE INCLUDED UNDER THAT
 ARTICLE.
  
 5} THE ARCHITECT MUST SIGN THE PLANS
 NOT RUBBER STAMP HIS NAME, PER
 61G1-16.003 FLORIDA ADMINISTRATIVE
 CODE, AND IS ENFORCED BY THIS
 DEPARTMENT. DO NOT SUBMIT PLANS IN
 VIOLATION OF THIS ARTICLE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  