2004-09-14 00:00:00BUILDING PLAN REVIEW
 PERMIT:04090102
 ADD:841 RIDGEWOOD DRIVE
 CONT:P&M CONTRACTORS
 TEL: (561)791-9777
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) FBC. 1005.4.4 EXCEPTIONS #3 WINDOW
 DOES NTO MEET THIS CODE.PLEASE ADDRESS
 THIS WINDOW.
 PROVIDE EMERGENCY EGRESS WINDOW IN
 SLEEPING ROOMS WITH A MINIMUM NET CLEAR
 OPENING HEIGHT OF 24INCHES,NET CLEAR
 OPENING WIDTH OF 20 INCHES AND NET CLEAR
 OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR
 OPENINGS ARE PERMITTED TO HAVE A NET
 CLEAR OPENING OF 5.0 SQ.FT. SILL HEIGHT
 SHALL NOT BE MORE THAN 44 INCHES ABOVE
 THE FLOOR.
  
 BUILDING PLAN REVIEW
 MYRON JACOBS
 TEL: (561)805-6726
 FAX: (561)659-8026