2004-11-23 00:00:00 | DENIED: |
| COMMENTS FROM PREVIOUS REVIEW NOT |
| ADDRESSED: |
| COMMENT #1 - ENERGY CALCULATIONS STILL |
| INDICATE SINGLE FAMILY.THIS IS A |
| MULTI-FAMILY STRUCTURE.RESPONSE |
| INDICTES THE CALCS WERE REVISED, BUT |
| THEY STILL INDICATE "SINGLE FAMILY, ONE |
| UNIT". |
| |
| COMMENT #3 - SINGLE PERMIT FOR THREE |
| BUILDINGS - PLEASE SEE COMMENT #1 BY |
| JIM |
| WITMER, BUILDING PLAN REVIEW. |
| |
| COMMENT #4 - BUILDING TYPE - RESPONSE |
| INDICATES PLAN SHEET A-1 FOR THE |
| BUILDING TYPE & GROUP.NO INDICATION |
| OF |
| TYPE V, VI ETC.SEE ALSO COMMENT #4 BY |
| JIM WITMER. |
| |
| COMMENT #6 - RETURN AIR FROM THE MASTER |
| BEDROOM.REVISED PLAN INDICATES AN 8", |
| 6" AND 4" SUPPLY AIR DUCT INTO THE |
| MASTER SUITE.THIS EQUALS A TOTAL OF |
| 91 |
| SQUARE INCHES. 10" RETURN EQUALS ON 78 |
| SQUARE INCHES. |
| |
| COMMENT #9 - ACCESS FOR THE AHU LOCATED |
| IN THE ATTIC SHALL BE IN ACCORDANCE |
| WITH |
| 2001 FBC CHAPTER 13 SUB-CHAPTER |
| 610.1.ABC.3.5.2 - RESPONSE INDICATES |
| DETAIL WAS ADDED TO SHEET A-9.NO |
| DETAIL OF THE ATTIC ACCESS IS SHOWN ON |
| A-9. |
| |
| PLEASE NOTE, A COPY OF THE ORIGINAL |
| PLANS SHOULD BE SUBMITTED WITH THE |
| CORRECTED SHEETS TO HELP EXPEDITE THE |
| RESUBMITTAL PROCESS. |
| |