2004-11-23 00:00:00DENIED:
 COMMENTS FROM PREVIOUS REVIEW NOT
 ADDRESSED:
 COMMENT #1 - ENERGY CALCULATIONS STILL
 INDICATE SINGLE FAMILY.THIS IS A
 MULTI-FAMILY STRUCTURE.RESPONSE
 INDICTES THE CALCS WERE REVISED, BUT
 THEY STILL INDICATE "SINGLE FAMILY, ONE
 UNIT".
  
 COMMENT #3 - SINGLE PERMIT FOR THREE
 BUILDINGS - PLEASE SEE COMMENT #1 BY
 JIM
 WITMER, BUILDING PLAN REVIEW.
  
 COMMENT #4 - BUILDING TYPE - RESPONSE
 INDICATES PLAN SHEET A-1 FOR THE
 BUILDING TYPE & GROUP.NO INDICATION
 OF
 TYPE V, VI ETC.SEE ALSO COMMENT #4 BY
 JIM WITMER.
  
 COMMENT #6 - RETURN AIR FROM THE MASTER
 BEDROOM.REVISED PLAN INDICATES AN 8",
 6" AND 4" SUPPLY AIR DUCT INTO THE
 MASTER SUITE.THIS EQUALS A TOTAL OF
 91
 SQUARE INCHES. 10" RETURN EQUALS ON 78
 SQUARE INCHES.
  
 COMMENT #9 - ACCESS FOR THE AHU LOCATED
 IN THE ATTIC SHALL BE IN ACCORDANCE
 WITH
 2001 FBC CHAPTER 13 SUB-CHAPTER
 610.1.ABC.3.5.2 - RESPONSE INDICATES
 DETAIL WAS ADDED TO SHEET A-9.NO
 DETAIL OF THE ATTIC ACCESS IS SHOWN ON
 A-9.
  
 PLEASE NOTE, A COPY OF THE ORIGINAL
 PLANS SHOULD BE SUBMITTED WITH THE
 CORRECTED SHEETS TO HELP EXPEDITE THE
 RESUBMITTAL PROCESS.
  