2004-11-16 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 04090032 |
| ADD: 1950 PRESIDENTIAL WAY |
| CONT: BAINES |
| TEL: (561)718-3997 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2ND REVIEW |
| ACTION: DENIED |
| |
| 1) COMMENT# 2FROM THE PREVIOUS REVIEW, |
| DELT WITH A SINGLE PERMIT COVERING 3 |
| BUILDINGS. THE BUILDING OFFIFIAL NEIL |
| MELICK WILL REQUIRE A SEPERATE PERMIT |
| FOR EACH BUILDING. A SEPERATE PERMIT |
| NUMBER WILL BE REQUIRED WITH ASSOCIATED |
| FEES AND REVIEWS. |
| |
| 2) COMMENT# 3 FROM THE PREVIOUS REVIEW, |
| THE PERMIT APPLICATION INDICATES (2 |
| LOTS): |
| 74-43-43-17-07-000-0051 |
| 74-43-43-17-07-000-0052 |
| THE PROPOSED BUILDING STRUCTURE |
| TRANSGRESSES LEGAL BOUNDARY LINES |
| BETWEEN THE LOTS WHICH COMBINE TO FORM |
| 'THE SITE'.A 'UNITY OF TITLE' SHALL |
| BE |
| RECORDED AT THE COUNTY COURTHOUSE. |
| SUBMIT A COPY OF THE RECORDED 'UNITY OF |
| OF TITLE' DOCUMENT SO THAT FBC TABLE |
| 600 |
| BOUNDARY LINE REQUIREMENTS MAY BE |
| DEEMED |
| NOT APPLICABLE. |
| |
| 3) COMMENT# 4 FROM THE PREVIOUS REVIEW, |
| 903.8.2 FLOR ST STATUTE 553.895(2) ALL |
| RESIDENTIAL BUILD. 3 OR MORE STORIES |
| TALL WHETHER DESIGNATED AS TOWNHOUSE, |
| CONDOMINIUMS, "APARTMENT HOUSES, |
| TENEMENTS, GARDEN APARTMENTS OR BY ANY |
| OTHER NAME SHALL BE SUPPLIED BY FIRE |
| SPRINKLERS MEETING NFPA 101. |
| |
| 4-A)COMMENT# 6 FROM THE PREVIOUS |
| REVIEW, |
| DEALS WITH THE SOILS REPORT, THE (3) |
| SETS OF SOILS REPORTS SUBMITTED ARE NOT |
| SIGNED NOR SEALED. FL STATE STATUTE |
| ADMINISTRATIVE CODE 61G15-23.002 |
| ENGINEERS, PLANS, |
| SPECIFICATIONS,REPORTS |
| OR OTHER DOCUMENTS PREPARED BY THE |
| DESIGN PROFESSIONAL AND BEING FILED FOR |
| PUBLIC RECORD SHALL HAVE THE SIGNATURE |
| AND OF THE DESIGN PROFESSIONAL AFFIXED |
| TO THE DOCUMENT. |
| FL STATE STAT: 61G15-23.002 ENGINEERS |
| FL ATATE STAT: 61G16.003 ARCHITECTS |
| 4-B) AUGER PILE NO INFORMATION HAS BEEN |
| SUBMITTED ON THE AUGER PILE S-1 |
| PROVIDES |
| THE LOCATION OF THE PILE BUT DIAMETER |
| NOR LENGHT IS NOT GIVEN NOR THE NUMBER |
| OF REBARS OR CAGES IN THE PILE? OR THE |
| LOADS TO BE RESISTED?PROVIDE THE |
| INFORMATION REQUIRED IN 1809 FOR |
| CAST-IN |
| -PLACE CONCRETE PILE. |
| 4-C PROVIDE DOCUMENTATION OF THE |
| GEO-TECH ENGINEERS OFFICE THAT WILL BE |
| SUPERVISING THE INSTALLATION OF THE |
| AUGER PILE AND SUBMITTING REPORTS. |
| |
| 5) COMMENT# 8 FROM THE PREVIOUS REVIEW, |
| EXTERIOR GUARDRAILS ARE TO BE 42" TALL, |
| SHEET A-3 2ND & 3RD STORY, SHEET A-6 |
| ALLINDICATE THE USE OF EXTERIOR |
| BALCONIES, REQUIREING 42" GUARDRAILS. |
| SEE 1015.2 HEIGHT, GUARDRAILS SHALL |
| FORM |
| A VERTICAL PROTECTIVE BARRIER OF NOT |
| LESS THAN 42" HEIGHT. |
| |
| 6)COMMENT# 10 FROM THE PREVIOUS REVIEW, |
| |
| ASSUMED PROPERTY LINES BETWEEN BUILDINGS |
| |
| ON THE SAME LOT. 705.1.1.2 EXTERIOR |
| WALLS WITHIN 15' OF ASSUMED PROPERTY |
| LINES REQUIRE OPENING PROTECTIVES. |
| SEE UNITS 1& 12/ 8&9. GARAGE DOORS, |
| EXTERIOR SWING DOORS AND WINDOWS LOCATED |
| WITHIN THE 15' FROM THE ASSUMED PROPERTY |
| LINE REQUIRE OPENING PROTECTIVES. |
| SEE THE BACK OF UNITS 1-4 & 9-12 ARE |
| ALSO LESS THAN 15' FROM THE PROPERTY |
| LINE.SEE TABLE 600 FOR TYPEV |
| NPROTECTED, |
| REQUIRES A (2) HR WALL FOR OPENINGS |
| LOCATED WITHIN 10'-20' FROM PROPERTY |
| LINES! THIS 2HR WALL REQUIRES THE |
| OPENING PROTECTIVES FOR SAID UNITS. |
| CONTRACTOR TO PROVIDE TESTING FOR SAID |
| WINDOWS AND DOORS. NOTE WINDOWS THAT |
| ARE |
| FIRE RATED ARE NOT LARGE MISSLE IMPACT |
| RATED, WILL NEED SHUTTERS. |
| |
| 7) COMMENT# 11 FROM THE PREVIOUS |
| REVIEW, |
| TABLE 600 FOR TYPE V BUILDING AT |
| 10'-20'WILL ALLOW 20% OPENINGS, THE |
| DIAGRAM SUBMITTED INDICATES COMPLIANCE |
| WITH TABLE 600 BUT THE ITEM NOT |
| CONSIDERED IN ALLOWABLE AREA IS THE |
| FLOOR TRUSSES FOR BOTH FLOORS, WHEN THIS |
| AREA IS DEDUCTED THE ALLOWABLE AREA |
| WOULD BE 328.2 SQFT. |
| THE WALL AREA IS CONSIDERED TO INCLUDE |
| THE AREA FROM FLOOR LEVEL TO THE CEILING |
| OF EACH STORY. THIS IS TAKEN FROM THE |
| CODE COMMENTARY, COMMENTARY ON TABLE |
| 600 |
| |
| |
| 8) FL BLD CODE 104.2.1.2 |
| ADDITIONAL INFORMATION REQUIRED, |
| COMMENT# 12 FROM THE PREVIOUS REVIEW, |
| SHEET A-7 WALL SECTION# 2, 3RD FLOOR IS |
| MISSING FLOOR LEDGER. |
| |
| 9) COMMENT# 13 FROM THE PREVIOUS |
| REVIEW, |
| 2309.7.1 VENTILATION OF ATTIC,DETAIL"A" |
| INDICATES THE INSULATION BLOCKING THE |
| ATTIC VENTILATION, HOW WILL THIS BE |
| CORRECTED. |
| |
| |
| 10)COMMENT# 14 FROM THE PREVIOUS REVIEW, |
| 1606.1.4(1) IN WIND BORNE DEBRIS |
| REGIONS, EXTERIOR GLAZING THAT RECEIVES |
| POSITIVE PRESSURE IN BUILDINGS SHALL BE |
| ASSUMED TO BE OPENINGS UNLESS SUCH |
| GLAZING IS IMPACT RESISTANT OR PROTECTED |
| WITH AN IMPACT RESISTANT COVERING MEET- |
| ING THE REQUIREMENTS OF SSTD 12, ASTM |
| E 1886 AND ASTM E 1996 OR MIAMI-DADE. |
| GLAZED OPENINGS LOCATED WITHIN 30 FT OF |
| GRADE SHALL MEET THE REQUIREMENTS OF |
| LARGE MISSLE TEST. |
| FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORTS,MISSING REPORTS ARE AS |
| FOLLOWS: |
| A) WINDOWS, FIXED & OPERATABLE |
| B) EXTERIOR DOORS, SLIDING, SWING OR |
| GARAGE DOORS |
| C) MULLIONS VERTICAL OR HORIZONTAL |
| D) STORM SHUTTERS- FOR FIRE RATED |
| OPENINGS |
| E) STRUCTURAL COMPONENTS- TRUSS ANCHORS |
| F) STRUCURAL COMPONENTS- EXTERIOR |
| RAILINGS |
| G) ROOFING ASSEMBLIES |
| PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 11) COMMENT# 15 FROM THE PREVIOUS |
| REVIEW, STORM SHUTTERS FOR FIRE RATED |
| OPENINGS.FL BLD CODE 2001 SECTION |
| 103.6, 1606.1.4, 1707.4 & 3401.7.2.4. |
| PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| SCHEDULE SUMMARIZING & IDENTIFYING |
| OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| BAR REINFORCING REQUIREMENTS, WALL PRES- |
| SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| SUBMITTED AT TIME OF PERMIT APPLICATION |
| TO FACILITATE PLAN REVIEW AND PERMIT |
| ISSUANCE. |
| |
| 12) COMMENT# 17 FROM THE PREVIOUS |
| REVIEW |
| 1707.4.3 EACH EXTERIOR DOOR ASSEMBLY |
| NOT COVERED BY 1707.4.2 |
| (GLAZED DOORS) SHALL BE LISTED AND TEST- |
| ED FOR A PERIOD EQUAL TO THE QUANITY |
| 3600/ V WHERE THE TIME PERIOD IS IN |
| SECTIONS AND V IS IN MILES PER HR TAKEN |
| FROM FIGURE 1606. THE TIME PERIOD SHALL |
| ALSO INCLUDE A 10 SECOND PERIOD AT A |
| LOAD EQUAL TO 1.5 TIMES THE DESIGN |
| PRESSURE. DADE COUNTY & SBCCI REPORTS |
| ARE ACCEPTED. |
| |
| 13) COMMENT# 18 FROM THE PREVIOUS |
| REVIEW |
| 1707.4.5.1 MULLIONS OCCURRING BETWEEN |
| INDIVIDUAL WINDOW AND GLASS |
| DOOR ASSEMBLIES. TESTING REPORTS ARE |
| REQUIRED BY AN APPROVED TESTING |
| LABORATORY OR BE ENGINEERED. |
| |
| 14) COMMENT# 19 FROM THE PREVIOUS |
| REVIEW |
| 1707.4.5.2 MULLIONS SHALL BE DESIGN- ED |
| TO TRANSFER THE DESIGN PRESSURE LOADS |
| APPLIED BY THE WINDOW OR DOOR ASSEMBLIES |
| TO THE ROUGH OPENING SUBTRATE. |
| |
| 15) COMMENT#20 FROM THE PREVIOUS REVIEW |
| RIBBED LATH, THE WEIGHT OF THE RIBBED |
| LATH HAS NOT BEEN PROVIDED FOR THE |
| HORIZONTAL SPANS SPECIFIED. |
| NOTE NO MENTION OF A VAPOR BARRIER |
| BEHIND THE WIRE LATH, ASTM C 1063. |
| |
| 16) COMMENT# 21 FROM THE PREVIOUS |
| REVIEW |
| 1503.4.4 PROTECTION AGAINST DECAY & |
| TERMITES. CONDENSATE LINES & ROOF DOWN |
| SPOUTS SHALL DISCHARGE AT LEAST 1 FT. |
| AWAY FROM THE STRUCTURE SIDEWALL, |
| WHETHER BY UNDERGROUND PIPING, TAIL EX- |
| TENSIONS, OR SPLASH BLOCKS. |
| NOTE COMMENT SHEET INDICATES SEE M-1, |
| NO SUCH PAGES SUBMITTED. |
| |
| 17) COMMENT# 22 FROM THE PREVIOUS |
| REVIEW |
| 1511.7 ROOF MOUNTED MECHANICAL UNIT S |
| SHALL BE MOUNTED ON CURBS RAISED A |
| MINIMUM OF 8 INCHES ABOVE THE ROOF SUR- |
| FACE, OR WHERE ROOFING MATERIALS EXTEND |
| BENEATH THE UNIT, ON RAISED EQUIPMENT |
| SUPPORTS PROVIDING A MINIMUM CLEARENCE |
| HEIGHT IN ACCORDANCE WITH TABLE 1511.7. |
| MECH. 301.13 WIND RESISTANCE MECHANICAL |
| EQUIPMENT, APPLIANCES AND SUP PORTS THAT |
| ARE EXPOSED TO WIND SHALL BE DESIGNED |
| AND INSTALLED TO RESIST THE WIND |
| PRESSURES ON THE EQUIPMENT & THE |
| SUPPORTS AS DETERMINED IN ACCORDANCE |
| WITH THE FL BLD CODE. THIS MAY BE ACCOMP |
| LISHED BY DESIGN OR BY APPLICATION OF |
| SECTION 301.13.1.NOTE: COMMENT SHEET |
| INDICATES A M-1, NO SUCH PAGES |
| SUBMITTED. |
| |
| 18) BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY. THE ACTUAL PERMIT |
| SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |