Plan Review Notes
Plan Review Notes For Permit 04090032
Permit Number 04090032
Review Stop B
Sequence Number 2
Notes
Date Text
2004-11-16 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04090032
 ADD: 1950 PRESIDENTIAL WAY
 CONT: BAINES
 TEL: (561)718-3997
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1) COMMENT# 2FROM THE PREVIOUS REVIEW,
 DELT WITH A SINGLE PERMIT COVERING 3
 BUILDINGS. THE BUILDING OFFIFIAL NEIL
 MELICK WILL REQUIRE A SEPERATE PERMIT
 FOR EACH BUILDING. A SEPERATE PERMIT
 NUMBER WILL BE REQUIRED WITH ASSOCIATED
 FEES AND REVIEWS.
  
 2) COMMENT# 3 FROM THE PREVIOUS REVIEW,
 THE PERMIT APPLICATION INDICATES (2
 LOTS):
 74-43-43-17-07-000-0051
 74-43-43-17-07-000-0052
 THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'.A 'UNITY OF TITLE' SHALL
 BE
 RECORDED AT THE COUNTY COURTHOUSE.
 SUBMIT A COPY OF THE RECORDED 'UNITY OF
 OF TITLE' DOCUMENT SO THAT FBC TABLE
 600
 BOUNDARY LINE REQUIREMENTS MAY BE
 DEEMED
 NOT APPLICABLE.
  
 3) COMMENT# 4 FROM THE PREVIOUS REVIEW,
 903.8.2 FLOR ST STATUTE 553.895(2) ALL
 RESIDENTIAL BUILD. 3 OR MORE STORIES
 TALL WHETHER DESIGNATED AS TOWNHOUSE,
 CONDOMINIUMS, "APARTMENT HOUSES,
 TENEMENTS, GARDEN APARTMENTS OR BY ANY
 OTHER NAME SHALL BE SUPPLIED BY FIRE
 SPRINKLERS MEETING NFPA 101.
  
 4-A)COMMENT# 6 FROM THE PREVIOUS
 REVIEW,
 DEALS WITH THE SOILS REPORT, THE (3)
 SETS OF SOILS REPORTS SUBMITTED ARE NOT
 SIGNED NOR SEALED. FL STATE STATUTE
 ADMINISTRATIVE CODE 61G15-23.002
 ENGINEERS, PLANS,
 SPECIFICATIONS,REPORTS
 OR OTHER DOCUMENTS PREPARED BY THE
 DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE
 AND OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 4-B) AUGER PILE NO INFORMATION HAS BEEN
 SUBMITTED ON THE AUGER PILE S-1
 PROVIDES
 THE LOCATION OF THE PILE BUT DIAMETER
 NOR LENGHT IS NOT GIVEN NOR THE NUMBER
 OF REBARS OR CAGES IN THE PILE? OR THE
 LOADS TO BE RESISTED?PROVIDE THE
 INFORMATION REQUIRED IN 1809 FOR
 CAST-IN
 -PLACE CONCRETE PILE.
 4-C PROVIDE DOCUMENTATION OF THE
 GEO-TECH ENGINEERS OFFICE THAT WILL BE
 SUPERVISING THE INSTALLATION OF THE
 AUGER PILE AND SUBMITTING REPORTS.
  
 5) COMMENT# 8 FROM THE PREVIOUS REVIEW,
 EXTERIOR GUARDRAILS ARE TO BE 42" TALL,
 SHEET A-3 2ND & 3RD STORY, SHEET A-6
 ALLINDICATE THE USE OF EXTERIOR
 BALCONIES, REQUIREING 42" GUARDRAILS.
 SEE 1015.2 HEIGHT, GUARDRAILS SHALL
 FORM
 A VERTICAL PROTECTIVE BARRIER OF NOT
 LESS THAN 42" HEIGHT.
  
 6)COMMENT# 10 FROM THE PREVIOUS REVIEW,
  
 ASSUMED PROPERTY LINES BETWEEN BUILDINGS
  
 ON THE SAME LOT. 705.1.1.2 EXTERIOR
 WALLS WITHIN 15' OF ASSUMED PROPERTY
 LINES REQUIRE OPENING PROTECTIVES.
 SEE UNITS 1& 12/ 8&9. GARAGE DOORS,
 EXTERIOR SWING DOORS AND WINDOWS LOCATED
 WITHIN THE 15' FROM THE ASSUMED PROPERTY
 LINE REQUIRE OPENING PROTECTIVES.
 SEE THE BACK OF UNITS 1-4 & 9-12 ARE
 ALSO LESS THAN 15' FROM THE PROPERTY
 LINE.SEE TABLE 600 FOR TYPEV
 NPROTECTED,
 REQUIRES A (2) HR WALL FOR OPENINGS
 LOCATED WITHIN 10'-20' FROM PROPERTY
 LINES! THIS 2HR WALL REQUIRES THE
 OPENING PROTECTIVES FOR SAID UNITS.
 CONTRACTOR TO PROVIDE TESTING FOR SAID
 WINDOWS AND DOORS. NOTE WINDOWS THAT
 ARE
 FIRE RATED ARE NOT LARGE MISSLE IMPACT
 RATED, WILL NEED SHUTTERS.
  
 7) COMMENT# 11 FROM THE PREVIOUS
 REVIEW,
 TABLE 600 FOR TYPE V BUILDING AT
 10'-20'WILL ALLOW 20% OPENINGS, THE
 DIAGRAM SUBMITTED INDICATES COMPLIANCE
 WITH TABLE 600 BUT THE ITEM NOT
 CONSIDERED IN ALLOWABLE AREA IS THE
 FLOOR TRUSSES FOR BOTH FLOORS, WHEN THIS
 AREA IS DEDUCTED THE ALLOWABLE AREA
 WOULD BE 328.2 SQFT.
 THE WALL AREA IS CONSIDERED TO INCLUDE
 THE AREA FROM FLOOR LEVEL TO THE CEILING
 OF EACH STORY. THIS IS TAKEN FROM THE
 CODE COMMENTARY, COMMENTARY ON TABLE
 600
  
  
 8) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 COMMENT# 12 FROM THE PREVIOUS REVIEW,
 SHEET A-7 WALL SECTION# 2, 3RD FLOOR IS
 MISSING FLOOR LEDGER.
  
 9) COMMENT# 13 FROM THE PREVIOUS
 REVIEW,
 2309.7.1 VENTILATION OF ATTIC,DETAIL"A"
 INDICATES THE INSULATION BLOCKING THE
 ATTIC VENTILATION, HOW WILL THIS BE
 CORRECTED.
  
  
 10)COMMENT# 14 FROM THE PREVIOUS REVIEW,
 1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
 GLAZED OPENINGS LOCATED WITHIN 30 FT OF
 GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS, FIXED & OPERATABLE
 B) EXTERIOR DOORS, SLIDING, SWING OR
 GARAGE DOORS
 C) MULLIONS VERTICAL OR HORIZONTAL
 D) STORM SHUTTERS- FOR FIRE RATED
 OPENINGS
 E) STRUCTURAL COMPONENTS- TRUSS ANCHORS
 F) STRUCURAL COMPONENTS- EXTERIOR
 RAILINGS
 G) ROOFING ASSEMBLIES
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 11) COMMENT# 15 FROM THE PREVIOUS
 REVIEW, STORM SHUTTERS FOR FIRE RATED
 OPENINGS.FL BLD CODE 2001 SECTION
 103.6, 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 12) COMMENT# 17 FROM THE PREVIOUS
 REVIEW
 1707.4.3 EACH EXTERIOR DOOR ASSEMBLY
 NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE. DADE COUNTY & SBCCI REPORTS
 ARE ACCEPTED.
  
 13) COMMENT# 18 FROM THE PREVIOUS
 REVIEW
 1707.4.5.1 MULLIONS OCCURRING BETWEEN
 INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 14) COMMENT# 19 FROM THE PREVIOUS
 REVIEW
 1707.4.5.2 MULLIONS SHALL BE DESIGN- ED
 TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 15) COMMENT#20 FROM THE PREVIOUS REVIEW
 RIBBED LATH, THE WEIGHT OF THE RIBBED
 LATH HAS NOT BEEN PROVIDED FOR THE
 HORIZONTAL SPANS SPECIFIED.
 NOTE NO MENTION OF A VAPOR BARRIER
 BEHIND THE WIRE LATH, ASTM C 1063.
  
 16) COMMENT# 21 FROM THE PREVIOUS
 REVIEW
 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
 NOTE COMMENT SHEET INDICATES SEE M-1,
 NO SUCH PAGES SUBMITTED.
  
 17) COMMENT# 22 FROM THE PREVIOUS
 REVIEW
 1511.7 ROOF MOUNTED MECHANICAL UNIT S
 SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
 MECH. 301.13 WIND RESISTANCE MECHANICAL
 EQUIPMENT, APPLIANCES AND SUP PORTS THAT
 ARE EXPOSED TO WIND SHALL BE DESIGNED
 AND INSTALLED TO RESIST THE WIND
 PRESSURES ON THE EQUIPMENT & THE
 SUPPORTS AS DETERMINED IN ACCORDANCE
 WITH THE FL BLD CODE. THIS MAY BE ACCOMP
 LISHED BY DESIGN OR BY APPLICATION OF
 SECTION 301.13.1.NOTE: COMMENT SHEET
 INDICATES A M-1, NO SUCH PAGES
 SUBMITTED.
  
 18) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026