Plan Review Notes
Plan Review Notes For Permit 04090032
Permit Number 04090032
Review Stop P
Sequence Number 1
Notes
Date Text
2004-10-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT P-1 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS.
 A) FIRST FLOOR TUB NOT VENTED, SECTION
 909.2.1 - SEE RED LINE CORRECTION.
 B) BATH #2 THIRD FLOOR TUB NOT VENTED.
 BATH #2 RED LINE CORRECTION SHOWN. SEC.
 901.2.1
 C) WASH MACHINE SHALL NOT DRAIN THROUGH
 THE WET VENT OF THE BATHROOM GROUP. SEC.
 909.1 - WASH MACHINE REQUIRES A STAND-
 PIPE, SECTIONS 1002.1/802.4 - W/M REQUI-
 RES A CLEANOUT 4' ABOVE THE FLOOR PER
 SECTION 708.10. - SEE RED LINE CORRECT-
 ION.
 D) MASTER BATH SHOWER & TUB NOT VENTED.
 SECTION 901.2.1 - SEE RED LINE CORRECT-
 ION.
 2) A WATER RISER DIAGRAM IS REQUIRED PER
 SECTION 104.3.1.1.
 3) AN RPZ BACKFLOW WILL BE REQUIRED FOR
 EACH BUILDING UNLESS EACH UNIT HAS AN
 INDIVIDUAL METER.
 4) IF AN RPZ BACKFLOW IS REQUIRED ON
 EACH BUILDING, THERMAL EXPANSION CONTROL
 WILL BE REQUIRED. THIS SHALL BE SHOWN ON
 THE WATER HEATER DETAIL. SEC. 607.3.2.
 5) A SEPARATE PERMIT & PLANS FOR IRRI-
 GATION WILL BE REQUIRED.
 6)ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  