2004-10-09 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1) SHT P-1 SANITARY RISER DIAGRAM DOES |
| NOT MEET CODE REQUIREMENTS. |
| A) FIRST FLOOR TUB NOT VENTED, SECTION |
| 909.2.1 - SEE RED LINE CORRECTION. |
| B) BATH #2 THIRD FLOOR TUB NOT VENTED. |
| BATH #2 RED LINE CORRECTION SHOWN. SEC. |
| 901.2.1 |
| C) WASH MACHINE SHALL NOT DRAIN THROUGH |
| THE WET VENT OF THE BATHROOM GROUP. SEC. |
| 909.1 - WASH MACHINE REQUIRES A STAND- |
| PIPE, SECTIONS 1002.1/802.4 - W/M REQUI- |
| RES A CLEANOUT 4' ABOVE THE FLOOR PER |
| SECTION 708.10. - SEE RED LINE CORRECT- |
| ION. |
| D) MASTER BATH SHOWER & TUB NOT VENTED. |
| SECTION 901.2.1 - SEE RED LINE CORRECT- |
| ION. |
| 2) A WATER RISER DIAGRAM IS REQUIRED PER |
| SECTION 104.3.1.1. |
| 3) AN RPZ BACKFLOW WILL BE REQUIRED FOR |
| EACH BUILDING UNLESS EACH UNIT HAS AN |
| INDIVIDUAL METER. |
| 4) IF AN RPZ BACKFLOW IS REQUIRED ON |
| EACH BUILDING, THERMAL EXPANSION CONTROL |
| WILL BE REQUIRED. THIS SHALL BE SHOWN ON |
| THE WATER HEATER DETAIL. SEC. 607.3.2. |
| 5) A SEPARATE PERMIT & PLANS FOR IRRI- |
| GATION WILL BE REQUIRED. |
| 6)ENGINEERS SHALL LEGIBLY INDICATE THEIR |
| NAME, ADDRESS AND LICENSE NUMBER ON EACH |
| SHEET. IF PRACTICING THROUGH A DULY |
| AUTHORIZED ENGINEERING BUSINESS, ENGIN- |
| EERS, ENGINEERS SHALL LEGIBLY INDICATE |
| THEIR NAME AND LICENSE NUMBER, AS WELL |
| AS, THE NAME, ADDRESS AND CERTIFICATE OF |
| AUTHORIZATION NUMBER OF THE ENGINEERING |
| BUSINESS ON EACH SHEET. A TITLE BLOCK |
| WILL SATISFY THIS REQUIREMENT. FAC |
| 61G15-23.002(2) - FS 471.025 |
| |