2004-10-12 00:00:00 | DENIED: |
| INSUFFICIENT INFORMATION FOR REVIEW. |
| PLEASE PROVIDE THE FOLLOWING: |
| |
| 1.ENERGY CALCULATIONS INDICATE "SINGLE |
| FAMILY".THIS IS CONSIDERED "MULTI |
| FAMILY". |
| |
| 2.PLAN INDICATES FOUR UNITS PER |
| BUILDING.ENERGY CALCUALTIONS DO NOT |
| SPECIFY INTERIOR UNIT TO EXTERIOR UNIT. |
| |
| 3.PLEASE CLARIFY ARE THESE UNITS TO |
| BE INDIVIDUALLY PERMITTED OR PERMITTED |
| BY BUILDING?SHOULD UNITS BE PERMITTED |
| INDIVIDUALLY, 2 COMPLETE SETS OF PLANS, |
| ENERGY & MANUAL J CALCS ARE REQUIRED FOR |
| EACH PERMIT APPLICATION. |
| |
| 4.INDICATE BUILDING TYPE.(TYPE V)? |
| |
| 5.MECHANICAL PLAN (M-1) INDICATES |
| OUTSIDE AIR CALCULATIONS, PLEASE SEE |
| TABLE 403.3 FOR REQUIRMENTS.INCLUDE |
| ALSO THE KITCHEN & BATHROOMS AS LISTED |
| ON TABLE 403.3. |
| |
| 6.RETURN AIR JUMPER FROM THE MASTER |
| BEDROOM IS NOT SIZED PROPERLY.ALL AIR |
| INTO THE MASTER SUITE IS TO BE INCLULDED |
| |
| 7.RETURN AIR JUMPER FROM BEDROOM 1 |
| ON THE FIRST FLOOR DOES NOT INDICATE |
| DUCT SIZE. |
| |
| 8.SUPPLY DUCT TO BEDROOM 2, NO DUCT |
| SIZE INDICATED. |
| |
| 9.MECHANICAL PLAN INDICATES ATTIC |
| ACCESS.PLEASE NOTE ACCESS SHALL BE |
| LOCATED WITHIN 6 FT OF THE SERVICE PANEL |
| AND SHALL COMPLY WITH 2001 FBC CHAPTER |
| 13 SUB-CHAPTER 610.1.ABC.3.5.2. |
| 10. PLEASE PROVIDE DETAIL OF DUCTWORK |
| BETWEEN THE WOOD TRUSS. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE |
| CONTACT PATTY KRAUSS AT (561) 805-6719. |