Plan Review Notes
Plan Review Notes For Permit 04090032
Permit Number 04090032
Review Stop ENG
Sequence Number 1
Notes
Date Text
2004-09-22 00:00:00FAILED:
 1. PLEASE NOTE THAT CIVIL PLAN SHEETS
 MUST HAVE THE ORIGINAL RAISED SEAL AND
 SIGNATURE OF THE CIVIL ENGINEER OF THE
 RECORD.
 2. ADDITIONAL CLEAN-OUT IN SEWER LINES
 SHOULD BE PROVIDED.
 3. PLEASE SHOW WHERE THE DUMPSTER
 ENCLOSURE WILL BE LOCATED.
 4. SIDEWALK ALONG THE PROPERTY IF
 DAMAGED DURING THE CONSTRUCTION MUST BE
 RESTORED TO THE ORIGINAL OR BETTER
 CONDITIONS.
 5. PLEASE SUBMIT CALCULATION FOR THE
 PROPOSED DRAINAGE SYS, INCLUDE PERVIOUS
 AND IMPERVIOUS AREAS FOR THE ENTIRE
 SITE
 6. CIVIL PLANS MUST BE APPROVED BY THE
 PUBLIC UTILITIES AND ENGINEERING FOR
 ALL
 THE CONNECTION TO THE SERVICES PRIOR
 GETTING APPROVAL FROM THE CONSTRUCTION
 SERVICES, PLEASE SUBMIT CIVIL PLANS
 ONLY
 ATT; MANNY GONZALEZ, 494-1085.
 7. ANY WORK WITHIN PUBLIC R.O.W
 REQUIRES
 A SEPARATE PERMIT FROM PUBLIC UTILITIES
 AND ENGINEERING, WINDEL PALMER
 494-1086.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI