Date |
Text |
2004-09-21 00:00:00 | ******** UNSAT ********* |
| |
| 1)NOTE: PLEASE SEE RISER DIAGRAM DOES |
| NOT SEEM TO INDICATE ANY MAINS?? 225.31, |
| 230.70 ETC. |
| GROUPING OF MAINS? 230.72 |
| |
| 2)NOTE: PLEASE SEE MISSING EQUIPMENT |
| GROUNDING CONDUCTORS FROM "MAINS" TO |
| PANELS. REQUIRED AFTER THE FIRST MEANS |
| OF DISCONNECT. 250.24 |
| |
| 3)NOTE: SMOKE DETECTORS ARE REQUIRED |
| INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| UNIT. |
| IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| TO FLOORS ABOVE AND IN THE VICINITY OF |
| BEDROOMS. |
| PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| A MIN OF 3' FROM BATHROOM DOORS AND |
| KITCHENS. |
| ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| |
| 4) NOTE: PLEASE LIST ALL THE REQ'D |
| DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| SCHEDULE. PER 210.52D, 210.11C3 |
| |
| 5)NOTE: PLEASE LIST THE REQ'D ARC |
| FAULT PROTECTED CURCUIT(S) ON PANEL |
| SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| IN BEDROOMS ARE TO BE PROTECTED , |
| INCLUDING, LTS, RECEPTS, SD'S ETC. |
| 210.12 2002 NEC. |
| PLEASE ALSO SEE SD'S ARE INDICATED AS |
| BEING ON THE KITCHEN LT CIRCUIT? |
| WILL THIS ALSO BE ARC FAULT PROTECTED? |
| PLEASE SEE NOTE #30 ON GENERAL NOTES. |
| SD'S REQUIRED TO BE ARC FAULT ALSO, SEE |
| ABOVE. |
| |
| 6)NOTE: PLEASE SEE DISCONNECTING CLEAR- |
| -ENCE FOR A/C UNIT. 110.26 |
| |
| 7)NOTE: PLEASE SUBMIT LOAD CALCULATIONS |
| FOR SERVICE. |
| |
| 8)NOTE: PLEASE SEE FAC 61G1-16.004 AND |
| FS 481.219 FOR MISSING REQUIRED INFOR- |
| -MATION ON TITLE BLOCK FOR ARCHITECT |
| FIRM. THIS IS REQUIRED ON ALL SHEETS |
| WHEATHER OR NOT COMMENT IS MADE BY |
| OTHER REVIEWERS. |
| PLEASE ALSO SEE PLANS ARE REQUIRED TO |
| HAVE AN ORIGINAL SIGNATURE AND TO BE |
| SEALED. 481.221. |
| |
| 9)NOTE: PLEASE VERIFY HOW MANY UNITS |
| THERE ARE GOING TO BE? ATTACHED? |
| SEPARATE SERVICES DETACHED BLDGS? |
| |
| PLEASE SEE POSSIBLE COMMENTS FROM OTHER |
| REVIEWERS WHICH MAY AFFECT ELECTRICAL |
| PLANS. |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| INSERT NEW SHEETS INTO COMPLETE SETS FOR |
| REVIEW AND STAMPING. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |