2004-10-13 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 04090032 |
| ADD: 1950 PRESIDENTIAL WAY |
| CONT: BAINES BUILDING COMPANY |
| TEL: (561)718-3997 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) THIS PROJECT SHALL BE REVIEWED AS |
| CONDOMINIUMS,THE PLANS INDICATE TOWN- |
| HOUSE. IF THE PROJECT IS TO CONTINUE AS |
| CONDOMINIUMS DELETE ALL REFRENCES TO |
| "TOWNHOUSE" ON ALL PLANS. IF THE PROJECT |
| IS TO CONTINUE AS TOWNHOUSE THEN THE |
| PLAT NEEDS TO BE REPLATED INTO INDIVID- |
| UAL LOTS. |
| |
| 2) THE SECOND ISSUE WILL BE THE PERMIT |
| COVERING THE 3 BUILDINGS UNDER ONE |
| SINGLE PERMIT. NO CERTIFICATE OF OCCU- |
| PANCY WILL BE ISSUED FOR ANY BUILDING |
| UNTIL ALL BUILDINGS ARE COMPLETE. |
| |
| 3) THE PROPOSED BUILDING STRUCTURE |
| TRANSGRESSES LEGAL BOUNDARY LINES |
| BETWEEN THE LOTS WHICH COMBINE TO FORM |
| 'THE SITE'.A 'UNITY OF TITLE' SHALL BE |
| RECORDED AT THE COUNTY COURTHOUSE. |
| SUBMIT A COPY OF THE RECORDED 'UNITY OF |
| OF TITLE' DOCUMENT SO THAT FBC TABLE 600 |
| BOUNDARY LINE REQUIREMENTS MAY BE DEEMED |
| NOT APPLICABLE. |
| |
| 4) 903.8.2 FLOR ST STATUTE 553.895(2) |
| ALL RESIDENTIAL BUILD. 3 OR MORE STORIES |
| TALL WHETHER DESIGNATED AS TOWNHOUSE, |
| CONDOMINIUMS, "APARTMENT HOUSES, |
| TENEMENTS, GARDEN APARTMENTS OR BY ANY |
| OTHER NAME SHALL BE SUPPLIED BY FIRE |
| SPRINKLERS MEETING NFPA 101. |
| |
| 5)PROVIDE ENERGY CALCULATIONS AND |
| EQUIPMENT SIZING CALCULATIONS (MANUAL J) |
| AS REQUIRED BY THE 2001 FLORIDA ENERGY |
| EFFICIENTCY CODE FOR BUILDING CONSTRUC- |
| TION. |
| THE ENERGY FORMS SUBMITTED ARE FOR A |
| SINGLE FAMILY USAGE, NOT WORST CASE FOR |
| CONDO "MULTIPLE FAMILY". |
| |
| 6) FL BLD CODE 1804.2.2 QUESTIONABLE |
| SOILS, WHERE THE BEARING CAPACITY IS |
| NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| WHERE THE BEARING CAPACITY OF THE SOIL |
| IS NOT DEFINITLY KNOWN OR IS IN QUESTION |
| THE BUILDING OFFICIAL MAY REQUIRE EXPLOR |
| ATIONS, TEST OR OTHER ADEQUATE PROOF AS |
| TO THE PERMISSIBLE SAFE BEARING |
| CAPACITY. REQUIRED TEST AND RECOMMENDA- |
| TIONS SUBMITTED TO VERIFY BEARING CAPA- |
| CITY SHALL BE CERTIFIED BY A GEOTECH- |
| NICALREPORT FROM A DESIGN PROFESSIONAL |
| PROPERLY LICENSED IN THE STATE OF |
| FLORIDA. |
| PROVIDE GEOTECHNICAL REPORT BY THE |
| TESTING LABS OF THE PALM BEACHES |
| FILE# 04/213-1. |
| IF THE REPORT DOES NOT PROVIDE INFORMA- |
| TION ON THE AUGER PILE INSTALATION, PRO- |
| VIDE INFORMATION REQUIRED IN 1809 FOR |
| CAST-IN-PLACE CONCRETE PILE.WHO WILL |
| SUPERVISE THE INSTALATION OF THE CAST |
| AUGER PILE? WIDTH OF PILE? |
| |
| 7) SHEET A-3 HAS NOTES ABOUT TOWNHOUSE |
| SEPERATION UL# U905 IF NOT TOWNHOUSE |
| DELETE NOTE, PROVIDE ACTUAL ASSEMBLY. |
| ALSO FOR UL# U465. |
| 104.2.1 W.P.B. ADMINISTRATIVE CODE |
| DRAWINGS & SPECIFICATIONS SHALL CONTAIN |
| INFORMATION, IN THE FORM OF NOTES OR |
| OTHERWISE, AS TO THE QUALITY OF |
| MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| CONFORMITY WITH THE TECHNICAL CODES. |
| SUCH INFORMATION SHALL BE SPECIFIC |
| AND THE TECHNICAL CODES "SHALL NOT BE |
| CITED AS A WHOLE OR IN PART, NOR THE |
| TERM "LEGAL" OR ITS RQUIVALENT BE USED |
| AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION". |
| |
| 8) ALSO SHEET A-3 2ND & 3RD LEVEL, SEE |
| GAURDRAILS: |
| 1015.2 HEIGHT. GUARDRAILS SHALL |
| FORM A VERTICAL PROTECTIVE BARRIER NOT |
| LESS THAN 42" HIGH. |
| 1015.3 OPENINGS. OPEN GUARDRAILS |
| SHALL HAVE INTERMEDIATE RAILS OR ORNA- |
| MENTAL PATTERNS SUCH AS A 4" DIAMETER |
| SPHERE CAN NOT PASS THROUGH. A BOTTOM |
| RAIL OR CURB SHALL BE PROVIDED THAT WILL |
| REJECT THE PASSAGE OF 2" DIAMETER |
| SPHERE. |
| ***GUARDRAILS WITHIN THE DWELLING UNIT |
| MAY BE 36" TALL. |
| |
| 9) SHEET A-3 FIRST FLOOR BATHROOM SHALL |
| REQUIRE A 29" CLEAR OPENING, SEE 11-11.1 |
| |
| 10)PROVIDE AN ASSUMED PROPERTY LINE |
| BETWEEN ALL BUILDINGS AS PER TABLE 600. |
| 705.1.1.2 EVERY EXTERIOR WALL WITHIN 15' |
| OF A PROPERTY LINE SHALL BE EQUIPPED |
| WITH OPENING PROTECTIVES, SEE UNITS |
| 1 & 12/ 8 & 9. GARAGE DOORS, WINDOWS & |
| EXTERIOR DOORS WITHIN 15' OF ASSUMED |
| PROPERTY LINE. |
| |
| 11) TABLE 600 ASSUMED PROPERTY LINE |
| BETWEEN BUILDINGS, PLANS DO NOT PROVIDE |
| IF THIS IS TYPE V OR VI CONSTRUCTION. |
| IF ASSUMED TYPE VI CONSTRUCTION, ASSUMED |
| PROPERTY LINE BETWEEN BUILDINGS PROVIDES |
| 40% ALLOWABLE OPENINGS. THE FIRST FLOOR |
| WITH GARAGE DOORS IS OVER THE ALLOWABLE |
| LIMIT OF 40% (FLOOR TO CEILING)THE |
| LENGHT OF THE BUILDING 10'-20'. IF BUILD |
| ING IS TYPE V THEN 10'-20' ALLOWABLE |
| OPENINGS ARE 20% (FLOOR TO CEILING). |
| |
| 12) FL BLD CODE 104.2.1.2 |
| ADDITIONAL INFORMATION REQUIRED, |
| SHEET A-7 WALL SECTION# 2, WHAT FLOOR |
| FRAMING IS SHOWN DIRECTLY BEHIND THE |
| LEDGER 3RD FLOOR FRAMING? ALSO IN SAME |
| DETAIL MISSING 2ND FLOOR CEILING FRAMING |
| AT WALL LINE. |
| |
| 13)2309.7.1 /103.7 VENTILATION OF ATTIC |
| SPACE VS. ALTERNATE MATERIALS & METHODS. |
| THE CODE ADVISORY BOARD DOES RECOGNIZE |
| THE ALTERNATE MATEERIALS AND CONDITIONS, |
| COMPLIANCE HAS NOT BEEN ACHIVED ON POINT |
| #3, WHEN UNVENTED ATTIC SYSTEMS ARE SPEC |
| IFIED IN CONJUNCTION WITH ASPHALT BASED |
| ROOFING PRODUCTS, THE ROOFING MATERIAL/ |
| SYSTEM MANUFACTURER SHALL PROVIDE AN |
| AFFIDAVIT CERTIFYING USE OF THEIR PRO- |
| DUCT OVER AN UNVENTED ATTIC SYSTEM. |
| |
| 14)1606.1.4(1) IN WIND BORNE DEBRIS |
| REGIONS, EXTERIOR GLAZING THAT RECEIVES |
| POSITIVE PRESSURE IN BUILDINGS SHALL BE |
| ASSUMED TO BE OPENINGS UNLESS SUCH |
| GLAZING IS IMPACT RESISTANT OR PROTECTED |
| WITH AN IMPACT RESISTANT COVERING MEET- |
| ING THE REQUIREMENTS OF SSTD 12, ASTM |
| E 1886 AND ASTM E 1996 OR MIAMI-DADE. |
| GLAZED OPENINGS LOCATED WITHIN 30 FT |
| OF GRADE SHALL MEET THE REQUIREMENTS OF |
| LARGE MISSLE TEST. |
| FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORTS,MISSING REPORTS ARE AS |
| FOLLOWS: |
| A) WINDOWS FIXED & OPERATABLE |
| B) EXTERIOR DOORS, SLIDING, SWING OR |
| GARAGE DOORS |
| C) MULLIONS VERTICAL & HORIZONTAL |
| D) STORM SHUTTERS |
| E) STRUCTURAL COMPONENTS- TRUSS ANCHORS |
| F) STRUCTURAL COMPONENTS- RAILINGS |
| G) ROOFING ASSEMBLIES |
| PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 15)STORM SHUTTERS: |
| PROVIDE STORM PANEL INFORMATION WITH |
| INSTALLATION SCHEDULE AND KEY PLAN WITH |
| SPECIFIC ANCHORS AND MOUNTING TO BE USED |
| FOR ALL NON-IMPACT GLAZING. |
| FBC 1606.1.4. |
| FL BLD CODE 2001 SECTION 103.6, |
| 1606.1.4, 1707.4 & 3401.7.2.4. |
| PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| SCHEDULE SUMMARIZING & IDENTIFYING |
| OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| BAR REINFORCING REQUIREMENTS, WALL PRES- |
| SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| SUBMITTED AT TIME OF PERMIT APPLICATION |
| TO FACILITATE PLAN REVIEW AND PREMIT |
| ISSUANCE. |
| |
| 16) 1606.4.4 ANCHOR METHODS. PROVIDE |
| INFORMATION FOR INSTALLATION OF DOOR |
| AND WINDOW BUCKS. |
| |
| 17) 1707.4.3 EACH EXTERIOR DOOR |
| ASSEMBLY NOT COVERED BY 1707.4.2 |
| (GLAZED DOORS) SHALL BE LISTED AND TEST- |
| ED FOR A PERIOD EQUAL TO THE QUANITY |
| 3600/ V WHERE THE TIME PERIOD IS IN |
| SECTIONS AND V IS IN MILES PER HR TAKEN |
| FROM FIGURE 1606. THE TIME PERIOD SHALL |
| ALSO INCLUDE A 10 SECOND PERIOD AT A |
| LOAD EQUAL TO 1.5 TIMES THE DESIGN |
| |
| 18) 1707.4.5.1 MULLIONS OCCURRING |
| BETWEEN INDIVIDUAL WINDOW AND GLASS |
| DOOR ASSEMBLIES. TESTING REPORTS ARE |
| REQUIRED BY AN APPROVED TESTING |
| LABORATORY OR BE ENGINEERED. |
| |
| 19) 1707.4.5.2 MULLIONS SHALL BE DESIGN- |
| ED TO TRANSFER THE DESIGN PRESSURE LOADS |
| APPLIED BY THE WINDOW OR DOOR ASSEMBLIES |
| TO THE ROUGH OPENING SUBTRATE. |
| |
| 20) FL BLD CODE 104.2.1.2 |
| ADDITIONAL INFORMATION REQUIRED, |
| SHEET A-7 DETAIL 2 INDICATES THE USE OF |
| PB GALVANIZED METAL, IS THIS FLAT OR |
| 3/8" RIBBED LATH? ASTM C 1063 FOR FLAT |
| DIAMOND LATH WEIGHT 2.5,2.75 OR 3.4 USE |
| ON CEILINGS ARE REDUCED: |
| 2.5= 12" |
| 2.75= 16" |
| 3.4= 16" |
| |
| 21) 1503.4.4 PROTECTION AGAINST DECAY & |
| TERMITES. CONDENSATE LINES & ROOF DOWN |
| SPOUTS SHALL DISCHARGE AT LEAST 1 FT. |
| AWAY FROM THE STRUCTURE SIDEWALL, |
| WHETHER BY UNDERGROUND PIPING, TAIL EX- |
| TENSIONS, OR SPLASH BLOCKS. |
| |
| 22)301.13.1 GROUND MOUNTED A/C UNITS: |
| GROUND-MOUNTED UNITS FOR R3 RESIDENTIAL |
| APPLICATIONS MAY BE ANCHORED WITH # 14 |
| SCREWS WITH GASKETED WASHERS ACCORDING |
| TO THE FOLLOWING: |
| 1) FOR UNITS WITH SIDES LESS THAN 12", |
| ONE SCREW SHALL BE USED AT EACH SIDE OF |
| THE UNIT. |
| 2) FOR UNITS BETWEEN 12" & 24", TWO |
| |
| 23) PROVIDE RISE & RUN OF STAIRS. |
| |
| 24)BEFORE A PERMIT TO CONSTRUCT, MAY |
| BE ISSUED, IMPACT FEES MUST BE PAID TO |
| PALM BEACH COUNTY. THE ACTUAL PERMIT |
| SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| THE PLANS WHEN RESUBMITTING PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIP- |
| TION OF THE REVISION MADE, IDENTIFYING |
| THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND, WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |