2004-11-15 00:00:00 | ********* UNSAT ********** |
| |
| 1)NOTE: PLEASE SEE SOME OF THE COMMENTS |
| |
| FROM FIRST REVIEW STILL NEED TO BE |
| ADDRESSED. |
| |
| 2)NOTE: PLEASE INCLUDE CWP AS PART OF |
| THE GROUNDING ELECTRODE SYSTEM. 250.50 |
| |
| 3)NOTE: PLEASE SEE NOT ALL SHEETS HAVE |
| THE PRINTED NAME AND SIGNATURE OF PERSON |
| RESPONSIBLE FOR PLAN, PLEASE ALSO SEE |
| RISER DIAGRAM. FBC 104.2.1 |
| |
| 4)NOTE: PLEASE SEE MISSING REQUIRED |
| DEDICATED BATH(S) CIRCUIT(S) PER 210.52D |
| AND 210.11C3 20A/#12 |
| |
| |
| 5 )NOTE: PLEASE LIST THE REQ'D ARC |
| FAULT PROTECTED CURCUIT(S) ON PANEL |
| SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| IN BEDROOMS ARE TO BE PROTECTED , |
| INCLUDING, LTS, RECEPTS, SD'S ETC. |
| |
| 6)NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| KITCHEN COUNTERSPACE AS GFI/GFI |
| PROTECTED. 210.8A6 |
| PLEASE ALSO SEE SPACING PER 210.52C1, |
| (ABOVE) WINE COOLER AND DW? |
| |
| 7)NOTE: PLEASE SEE TWO DIFFERENT |
| ELECTRICAL DRAWINGS FOR KITCHEN WAS |
| SUBMITTED? |
| |
| 8)NOTE: PLEASE SUBMIT LOAD CALCULATIONS |
| PER 220.31B |
| 215.5 |
| |
| 8)NOTE: PLEASE SEE EACH ROOM IS SHOWN ON |
| AN INDIVIDUAL SHEET. UNABLE TO CLEARLY |
| SEE WHERE SD'S WOULD BE LOCATED OUTSIDE |
| BEDRMS. |
| NFPA-71 8-1.4.1.6.2 |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL.' |
| |