Plan Review Notes
Plan Review Notes For Permit 04081463
Permit Number 04081463
Review Stop E
Sequence Number 2
Notes
Date Text
2004-11-15 00:00:00********* UNSAT **********
  
 1)NOTE: PLEASE SEE SOME OF THE COMMENTS
  
 FROM FIRST REVIEW STILL NEED TO BE
 ADDRESSED.
  
 2)NOTE: PLEASE INCLUDE CWP AS PART OF
 THE GROUNDING ELECTRODE SYSTEM. 250.50
  
 3)NOTE: PLEASE SEE NOT ALL SHEETS HAVE
 THE PRINTED NAME AND SIGNATURE OF PERSON
 RESPONSIBLE FOR PLAN, PLEASE ALSO SEE
 RISER DIAGRAM. FBC 104.2.1
  
 4)NOTE: PLEASE SEE MISSING REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) PER 210.52D
 AND 210.11C3 20A/#12
  
  
 5 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 6)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI
 PROTECTED. 210.8A6
 PLEASE ALSO SEE SPACING PER 210.52C1,
 (ABOVE) WINE COOLER AND DW?
  
 7)NOTE: PLEASE SEE TWO DIFFERENT
 ELECTRICAL DRAWINGS FOR KITCHEN WAS
 SUBMITTED?
  
 8)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 PER 220.31B
 215.5
  
 8)NOTE: PLEASE SEE EACH ROOM IS SHOWN ON
 AN INDIVIDUAL SHEET. UNABLE TO CLEARLY
 SEE WHERE SD'S WOULD BE LOCATED OUTSIDE
 BEDRMS.
 NFPA-71 8-1.4.1.6.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.'
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]