2004-10-20 00:00:00 | CHECKLIST: |
| 1-PAY IMPACT FEES TO PALM BEACH COUNTY. |
| BRING BACK STAMPED DRAWINGS & RECEIPT. |
| 2-SH24 EGRESS WINDOWS DON'T MEET THE |
| REQUIREMENTS OF SEC. 1005.4.4 FBC 2001 |
| WHERE NET CLEAR HEIGHT DIMENSION SHALL |
| BE 24". ALSO, SEE SEC. 1005.4.1 CITY |
| AMENDMENTS FOR ADDITIONAL REQUIREMENTS |
| **WINDOW SIZE SHOWN ON ELEVATIONS ARE NO |
| TO SCALE ACCORDING TO SIZE CALLED ON |
| FLOOR PLANS. REVISE AS REQUIRED. |
| 3-SPECIFY CONCRETE SLAB JOINTS OR |
| SPECIFY WWM SUPPORTS AND SPACING AS |
| REQ'D BY SEC. 1909.3 FBC 2001. |
| 4-SHEET 3/7 FOOTING F08.08(T.E) DOESN'T |
| MATCH FOOTING SHOWN ON SCHEDULE. |
| 5-SHEET 4/7: SPECIFY ATTIC LIVE LOAD |
| REQUIRED FOR TRUSSES DESIGN. SEE |
| TABLE 1604.1 FBC 2001 (AND SPECIFY |
| STORAGE OR NON STORAGE). |
| 6-CONTRACTOR TO UPDATE LICENSE. SEE |
| PERMIT CLERK AT FRONT COUNTER. |
| 7-OWES $341.31 FOR UPDATED VALUATION. |
| PAY ATTACHED RECEIPT. |
| 8-STORM SHUTTERS:A)INSTALLATION SCHEDULE |
| SHOWS ENTRY DOOR BLOCKED WITH STORM |
| PANELS. SPECIFY WHICH ONE IS THE MEANS |
| OF ESCAPE REQUIRED BY SEC. 1005.4.5 |
| FBC 2001. |
| B)PROVIDE CORRECT FL. PRODUCT APPROVAL |
| THAT MATCHES DADE COUNTY REPORT. |
| C)REVISE ANCHOR SCHEDULE. SEE APPROVED |
| DRAWINGS AND SPECIFY ANCHOR TYPE AND |
| SPACING ACCORDING TO THE DESIGN PRE- |
| SSURES, EDGE DISTANCE, PANEL SPAN, |
| CONNECTION TYPE AND STRUCTURE TO BE |
| ATTACHED (CONCRETE BLOCK OR CONCRETE). |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC |
| 9-IF CEILING FAN CREDIT IS TAKEN ON THE |
| ENERGY CALCS, THEN, NEED TO SPECIFY |
| FANS SIZES ON PLANS AS PER TABLE 6-6 |
| OF CHAPTER 13 FBC 2001. |
| 10-PROVIDE STRUCTURAL BUCK DETAIL FOR |
| ENTRY DOOR USING 2X BUCK AS REQUIRED |
| BY DOOR PRODUCT APPROVAL. |
| 11-PROVIDE FLORIDA OR LOCAL PRODUCT |
| APPROVAL FOR: A)ENTRY DOOR THAT MATCH |
| DOOR SHOWN ON PLANS. PRODUCT APPROVAL |
| SUBMITTED IS FOR GLASS DOOR. REVISE |
| PLANS AND PRODUCT APPROVAL TO MATCH. |
| B)SLIDING GLASS DOORS WITH CORRECT FL. |
| PRODUCT APPROVAL NUMBER. |
| C)SINGLE HUNG WINDOWS WITH CORRECT FL. |
| PRODUCT APPROVAL NUMBER. |
| D)STRUCTURAL CONNECTORS SPECIFIED: |
| SIMPSON AND USP CONNECTORS. |
| E)GARAGE DOOR WITH LEGIBLE DRAWINGS. |
| |
| 12-SHEET 4/7: A)SPECIFY FASTENERS FOR |
| 2X8 TOP PLATE. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| B)REVISE NUMBER OF FASTENERS SPECIFIED |
| FOR SIMPSON SPH8. SEE 2004 SIMPSON |
| CATALOGUE. |
| **SEE PLANS FOR ADDITIONAL COMMENTS. |
| |
| 13-PROVIDE SOIL TEST REPORT. |
| |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| JULIO GOMEZ AT 805-6712. |