2004-09-16 00:00:00******* UNSAT *******
  
 PLEASE SEE NOTES FROM FIRST REVIEW STILL
 NEED TO BE ADDRESSED.
  
 1)NOTE: PLEASE SEE FBC 104.2.1, PLANS
 ARE REQUIRED TO HAVE PRINTED NAME AND
 SIGNATURE OF PERSON RESPONSIBLE FOR
 PLANS/DESIGN.
  
 2)NOTE: PLEASE SEE A RISER DIAGRAM IS
 NOW BEING SUBMITTED, HOWEVER NO AIC
 RATING FOR EQUIPMENT IS BEING INDICATED
 AS REQUESTED ON PREVIOUS REVIEW.
 110.9/215.5
  
 3)NOTE: PLEASE VERIFY METHOD OF
 EQUIPMENT GROUNDING FROM MAIN TO PANEL,
 IS THIS RIGID ALSO? ONLY IF PVC.
 250.24
  
 4)NOTE: PLEASE SEE 210.52E FOR MISSING
 FRONT AND REAR RECEPTS.
  
 5)NOTE: PLEASE SEE SD'S ARE INDICATED
 ON SEPARATE CIRCUIT WHICH IS PERMITTED,
 THESE ARE ALSO REQUIRED TO BE ARC-FAULT
 PER 210.12 OF 2002 NEC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  