Plan Review Notes For Permit 04081345 |
Permit Number |
04081345 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-08-31 00:00:00 | | | PLEASE PROVIDE A RISER DIAGRAM PER 215.5 | | WITH AIC RATINGS PER 110.9 | | | | PLEASE PROVIDE A PANEL SCHEDULE SO THAT | | BC WIRE, OCP SIZES AND REQUIRED CIRCUIT | | COMPLIANCE CAN BE DETERMINED. | | | | ALL INFORMATION/DRAWINGS/SPECIFICATIONS | | AND ACCOMPANYING DATA SHALL BEAR THE | | NAME AND SIGNATURE OF THE PERSON | | RESPONSIBLE FOR THE DESIGN. SECTION | | 104.2.1 FBC. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|