Plan Review Notes For Permit 04081182 |
Permit Number |
04081182 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-09-20 00:00:00 | DENIED: | | PER FS 471.025 AND THE FAC 61G15-23.002, | | LICENSE NUMBER SHALL BE INCLUDED ON THE | | TITLE BLOCK AND PLANS ARE TO SIGNED NOT | | INITIALED BY THE ENGINEER.SEE ALSO | | COMMENT #2 BY BUILDING PLAN REVIEW. | | | | RETURN AIR JUMPERS ARE NOT SIZED | | PROPERLY.PER 2001 FBC(M) 601.4 | | EXCEPTION #1, RETURN AIR JUMPERS SHALL | | BE 1 1/2 TIMES THE SQUARE INCHES OF THE | | SUPPLY.ALL AIR INTO THE MASTER SUITE | | SHALL BE INCLUDED PER #3 OF 601.4. | | | | CONDENSATE SHALL DISCHARGE A MINIMUM OF | | 12" AWAY FROM THE BUILDING STRUCTURE PER | | 2001 FBC 1503.4.4. | | | | AUXILIARY DRAIN PAN WITH OVERFLOW | | PROTECTION REQUIRED PER 2001 FBC(M) | | 307.2.3. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|