Notes
Date Text
2004-09-20 00:00:00DENIED:
 PER FS 471.025 AND THE FAC 61G15-23.002,
 LICENSE NUMBER SHALL BE INCLUDED ON THE
 TITLE BLOCK AND PLANS ARE TO SIGNED NOT
 INITIALED BY THE ENGINEER.SEE ALSO
 COMMENT #2 BY BUILDING PLAN REVIEW.
  
 RETURN AIR JUMPERS ARE NOT SIZED
 PROPERLY.PER 2001 FBC(M) 601.4
 EXCEPTION #1, RETURN AIR JUMPERS SHALL
 BE 1 1/2 TIMES THE SQUARE INCHES OF THE
 SUPPLY.ALL AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED PER #3 OF 601.4.
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE PER
 2001 FBC 1503.4.4.
  
 AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  