Plan Review Notes
Plan Review Notes For Permit 04081182
Permit Number 04081182
Review Stop E
Sequence Number 1
Notes
Date Text
2004-09-15 00:00:00******** UNSAT *******
  
 1)NOTE: PLEASE SEE TITLE BLOCK FOR ENGI-
 -NEER REQUIRED TO HAVE PRINTED LICENSE
 #. 61G15-23.002
 PLEASE ALSO SEE FS 471.023, A LEGAL
 SIGNATURE IS REQUIRED. APPEARS TO BE
 INITIALS??
  
 2)NOTE: PLEASE SEE TITLE BLOCK FOR
 DESIGN AND ASSC'S. FS 481.219, 61G1-16.-
 -.004. PLEASE INCLUDE ALL LICENSE INFOR-
 -MATION.
  
 3)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4.1.6.2
  
 4)NOTE: PLEASE CORRRLELATE SIZE OF HEAT/
 KW WITH MECHANICAL SPECS. PLEASE ALSO
 SEE 424.3B FOR REQUIRED MIN OCP OF 125%.
  
 5 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 2002 NEC 210.12
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  