2004-09-15 00:00:00 | ******** UNSAT ******* |
| |
| 1)NOTE: PLEASE SEE TITLE BLOCK FOR ENGI- |
| -NEER REQUIRED TO HAVE PRINTED LICENSE |
| #. 61G15-23.002 |
| PLEASE ALSO SEE FS 471.023, A LEGAL |
| SIGNATURE IS REQUIRED. APPEARS TO BE |
| INITIALS?? |
| |
| 2)NOTE: PLEASE SEE TITLE BLOCK FOR |
| DESIGN AND ASSC'S. FS 481.219, 61G1-16.- |
| -.004. PLEASE INCLUDE ALL LICENSE INFOR- |
| -MATION. |
| |
| 3)NOTE: SMOKE DETECTORS ARE REQUIRED |
| INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| UNIT. |
| IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| TO FLOORS ABOVE AND IN THE VICINITY OF |
| BEDROOMS. |
| PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| A MIN OF 3' FROM BATHROOM DOORS AND |
| KITCHENS. |
| ABOVE PER:FBC 905.2, NFPA-72 8-1.4.1.6.2 |
| |
| 4)NOTE: PLEASE CORRRLELATE SIZE OF HEAT/ |
| KW WITH MECHANICAL SPECS. PLEASE ALSO |
| SEE 424.3B FOR REQUIRED MIN OCP OF 125%. |
| |
| 5 )NOTE: PLEASE LIST THE REQ'D ARC |
| FAULT PROTECTED CURCUIT(S) ON PANEL |
| SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| IN BEDROOMS ARE TO BE PROTECTED , |
| INCLUDING, LTS, RECEPTS, SD'S ETC. |
| 2002 NEC 210.12 |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |