Plan Review Notes
Plan Review Notes For Permit 04081159
Permit Number 04081159
Review Stop E
Sequence Number 1
Notes
Date Text
2004-09-01 00:00:00************* UNSAT *************
  
 1)NOTE: PLEASE SEE PLANS ARE NOT SIGNED
 DATED AND SEALED BY THE ARCH SHOWN ON
 TITLE BLOCK.
  
 2)NOTE: PLEASE SEE 2002 NEC 210.12 FOR
 NEW CIRCUIT TO BEDRM.
  
 3)NOTE: PLEASE SEE PERMIT APPLICATION
 DOES NOT MENTION BATH REMOD YET PLANS
 INDICATE THIS??
  
 4)NOTE: PLEASE SEE 210.52D/210.11C3
 BATH CIRCUIT TO BE 20A #12.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  